Carrier 48ZG User's Information Manual
Carrier 48ZG User's Information Manual

Carrier 48ZG User's Information Manual

Gas heating/electric cooling units with comfortlink controls
Hide thumbs Also See for 48ZG:

Advertisement

Quick Links

User's Information Manual
NOTE TO INSTALLER:
This manual should be left with the equipment owner.
WARNING: If the information in this
manual is not followed exactly, a fire or
explosion may result causing property
damage, personal injury or loss of life.
— Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch;
do not use any phone in your
building.
• Immediately call your gas supplier
from a neighbor's phone. Follow the
gas supplier's instructions.
• If you cannot reach your gas sup-
plier, call the fire department.
— Installation and service must be per-
formed by a qualified installer, service
agency or the gas supplier.
Improper installation, adjustment, alteration, service, or
maintenance can cause injury or property damage. Refer to
this manual. For assistance or additional information, con-
sult a qualified installer, service agency, or the gas supplier.
Before performing recommended maintenance, be sure
main power switch to unit is turned off. Electrical shock
could cause personal injury.
Your combination heating/cooling rooftop unit is equipped
with an automatic direct spark ignition system and induced-
draft power combustion blower.
Do not attempt to light by hand; personal injury may result.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480045-01
Book 1
Tab
1a
Gas Heating/Electric Cooling Units
with COMFORTLINK™ Controls
1. Do not turn off the electrical power to unit without
first turning off the gas supply.
2. Before attempting to start the gas heating section,
familiarize yourself with all the procedures that must
be followed.
3. Never attempt to manually light the unit with a match,
lighter, or any other flame. If the electric sparking de-
vice fails to light the burners, refer to the shutdown
procedures, then call your dealer as soon as possible.
If you do not follow these instructions exactly, a fire or
explosion may result, causing property damage, injury, or
loss of life.
See Fig. 1 for location of gas valve(s). Refer to Fig. 2 while
proceeding with the following steps.
1. Turn off the unit demand for cooling or heating by using
the scrolling marquee. The scrolling marquee is located in
the control box at the compressor end of the unit.
a. Push the
is shown.
b. Push the
lit.
c. Push the
STOP.
d. Push the
will flash.
e. Push the
YES and then push
locked off from heating, cooling or any operation.
The controls will still function and the display will
still operate.
2. Close the field-installed manual gas shutoff valve.
3. Turn off the electrical power to the unit using the optional
disconnect or the field-installed disconnect and lock off
using proper lockout and tag-out procedures.
4. Open the burner section hinged access door.
5. Move the switch on the gas valves to the OFF position
and wait 5 minutes.
NOTE: If this is the first installation of the unit, the gas
flue hoods must be installed before operating unit. These
must be installed for the unit to run properly.
6. Move the switch on the gas valves to the ON position.
7. Close the burner section hinged access door.
8. Turn on the electrical supply to the units.
9. Open the field-installed manual gas valve.
Printed in U.S.A.
Form 48Z-5SO
48ZG,ZN030-105
48ZT,ZW,Z6,Z8075-105
TO LIGHT UNIT
ESCAPE
key unit a blank display screen
key until the SERVICE TEST LED is
ENTER
key. The display will show
ENTER
key again. The NO/YES display
or
key to toggle the display to
ENTER
. The unit will be
Pg 1
7-07
Replaces: 48Z-3SO

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 48ZG

  • Page 1 8. Turn on the electrical supply to the units. 9. Open the field-installed manual gas valve. Printed in U.S.A. Form 48Z-5SO Pg 1 48ZG,ZN030-105 key unit a blank display screen key. The display will show key again. The NO/YES display key to toggle the display to ENTER .
  • Page 2 NOTE: High heat consists of sections 1 and 2. Low heat consists of section 1 only. 030-050 SIZES 10. Using the scrolling marquee, enable the unit to run using the following procedure: ESCAPE a. Push the key unit a blank display screen is shown.
  • Page 3 MODE Run Status Service Test Temperature Pressures Setpoints Alarm Status Inputs Outputs ESCAPE ENTER Configuration Time Clock Operating Modes Alarms STEP 1 STEP 4 a48-8298 STEP 6 STEP 8 STEP 2 STEP 5 STEP 7 MODE Run Status Service Test Temperature Pressures Setpoints...
  • Page 4: To Shut Unit Off

    TO SHUT UNIT OFF Do not turn off the electrical power to unit without first turning off the gas supply. Never attempt to manually light the main burners on a unit with a match, lighter, or any other flame. If the electric sparking device fails to light the main burn- ers, refer to the following shut off procedure, then call your dealer as soon as possible.
  • Page 5 When replacing your unit filters, always use the same size and type of filter that was originally supplied by the installer. Units with outdoor air capability have a cleanable filter for the outdoor air. This filter should be checked annually and cleaned as necessary.
  • Page 6 FLUE OUTLETS (FAR SIDE) CONTROL BOX GAS SECTION ACCESS DOOR (FAR SIDE) Fig. 4 — Door Locations (48Z Series Units) SIZES 030-050 (040 SHOWN) SIZES 055-070 ACCESS DOOR ACCESS DOOR (NEAR SIDE ONLY) ACCESS DOOR (FAR SIDE ONLY) (BOTH SIDES) ACCESS DOOR (FAR SIDE ONLY) FILTER...
  • Page 7 Periodically check the condition of fan Fan and Belts — wheels and housings and belt tension. When service is neces- sary, call your dealer. Evaporator-Fan Motor, Condenser-Fan Motor and Combustion-Fan Motor — recommended. Bearings will not require lubrication for at least 5 years of normal operation.
  • Page 8: Regular Dealer Maintenance

    Complete Service Instructions can be found in the base unit Controls, Start-Up, Operation, Service and Troubleshooting literature. Copyright 2007 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 Catalog No.

This manual is also suitable for:

Z648ztZ8075-105Zn030-105Zw48zn ... Show all