Horizontal And Vertical Economi$Er; Accessory Installation Instructions - Carrier 40QQ-036ABA3-0A0 Installation Instructions Manual

Vrf rooftop heat recovery and heat pump
Table of Contents

Advertisement

To use the alternate bottom drain connection, remove the
red drain plug from the bottom connection (use a 1/2 inch
square socket drive extension), and install it in the side
drain connection.
The piping for the condensate drain and external trap can
be completed after the unit is in place. See Fig. 13.
MINIMUM PITCH
1" (25mm) PER
BASE RAIL
10' (3m) OF LINE
OPEN
VENT
TO ROOF
DRAIN
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4" (102) trap is recommended
Fig. 13 - Condensate Drain Piping Details
All units must have an external trap for condensate
drainage. Install a trap at least 4 inches (102mm) deep and
protect against freeze-up. If drain line is installed
downstream from external trap, pitch line away from the
unit at 1 inch per 10 feet (25mm per 3m) of run. Do not
use a pipe size smaller than the unit connection (3/4 inch).
Step 9 — Make Electrical Connections
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of
personal injury if an electrical fault should occur. This
ground may consist of an electrical wire connected to
the unit ground lug in the control compartment, or
conduit approved for electrical ground when installed
in accordance with NEC; ANSI/NFPA 70, latest
edition (in Canada, Canadian Electrical Code CSA
[Canadian Standards Association] C22.1), and local
electrical codes.
NOTE:
Field- supplied wiring shall conform to the
limitations of minimum 63_F (33_C) rise.
Field Installed Smoke Detector
Field installed Smoke Detector by 3
When smoke detector is required by the building codes, it
must
be
installed
and
vendor. Carrier offers the Totaline
detector model# P270- 3000PL. Recommended wiring
requires using the dry contacts to cut power to the L1 or
L2 power wiring coming into TB1.
2˝ (51) MIN
SEE NOTE
ROOF
CURB
DRAIN PLUG
.
rd
party
wired
by
a
third- party
®
4- Wire Duct Smoke
Typical Sequence of Operation:
Smoke Detector error
S Dry contacts on smoke detector open/close
S L2 is opened and power is removed from fan coil
S VRF CDU has error due to lost fan coil
Smoke Detector returns to normal operation after
error
S Dry contacts on smoke detector open/close
S L2 has continuity to the FCU
S VRF CDU can regain communication to FCU
Step 10 — Install Accessories
Available accessories include:
S Curb
S Electric heaters and single- point connection kits
S EconoMi$er X (with control)
Table 4 – Factory Default DIP Switch Settings for Fan
Control Board
DIP Switch
1
OFF
ON
OFF
ON
HORIZONTAL AND VERTICAL
ECONOMI$ER X ACCESSORY
INSTALLATION INSTRUCTIONS
Read these instructions completely before attempting to
install the
Horizontal EconoMi$er X Accessory.
SAFETY CONSIDERATIONS
Installation and servicing of air- conditioning equipment
can be hazardous due to system pressure and electrical
components. Only trained and qualified service personnel
should
install,
repair,
equipment.
Untrained personnel can perform the basic maintenance
functions of replacing filters. All other operations should
be performed by trained service personnel. When working
on air- conditioning equipment, observe precautions in the
literature, tags, labels attached to the unit, and other safety
precautions that may apply. Follow all safety codes. Wear
safety glasses and work gloves.