En vi ron men tal Pro tec tion Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 Agency (EPA) and the De part ment of Energy (DOE). Because it is lowest in CO...
In ideal con di tions, an open loop ap pli ca tion can be the most eco nom i cal type of system to install. Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 Indoor & Outdoor Split...
This eliminates uneven peaks and valleys Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 and allows for steady cooling comfort. Homeowners now have a better, more effi cient way to power their heating and cooling system, raising their level of comfort, while lowering energy bills.
Our IPCS system: - Verifi es that the correct components are being assembled. Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 Two-Stage Indoor Split Puron Systems ®...
Page 8
• Closed loop Flow Controller. • Electronic auto-changeover thermostat with 3- stage heat, 2-stage cool and indicator LED’s. • Hose kits. Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 Advanced Unit Controls With Easy Diagnostics And Unit Protection Sentinel Functions...
Page 9
Fully Insulated Installed Hot Water Water and Genorator With Refrigerant Lines Internal Pump Low Profi le Control Box Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 Two-Stage Indoor Split Puron Systems ® Brass Swivel Water Connections Backseating Brass...
• LED Fault and status indication with memory for easy diagnostics. • Designed for front-access service in tight ap pli ca tions. Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 • High and low pressure service ports in the refrigerant circuit.
Page 11
Stackable Cabinet Digital Controls Copeland Scroll Compressors Easy Service Access From Three Sides 1” Brass Swivel Water Connections Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 Single-Stage Indoor Split R22 Systems Fully Insulated Water and Refrigerant Lines...
3 times larger than the new construction market). Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 In new construction, the GT-S offers many benefi ts over packaged geothermal units: The fl uid loop is kept outside, which keeps large diameter piping, fl...
Page 13
Its effi ciency and application fl exibility make it the “Paradigm” of geothermal heat pumps. Air Handler TXV “IN” toward outdoor condensing unit Fossil Furnace Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 Single-Stage Outdoor Split R22 Systems TXV “IN” toward outdoor condensing Unit...
• LED Fault and status indication with memory for easy diagnostics. Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 • High and low pressure service ports in the refrigerant circuit. • Refrigerant sensing freeze protection for more accurate low temperature cut-out.
Page 15
Heavy Gauge Steel Insulated Weather Resistant Cabinet Integral Carrying Handles Internally Mounted Flow Controller Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 Single-Stage Outdoor Split R22 Systems Copeland Scroll Compressor (Rotary in 018) Digital Controls Hot Water...
Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature. Heating capacities based upon 68°F DB, 59°F WB entering air temperature. All ratings based upon 208V operation. Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 Ground Water Heat Pump Heating 68°F Cooling 59°F...
Page 22
See performance correction tables for operating conditions other than those listed above. “-” HWG operation is limited by a discharge temperature switch. Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 50YDS026 Full Load With FV4003 Cooling - EAT 80/67°F...
Page 24
See performance correction tables for operating conditions other than those listed above. “-” HWG operation is limited by a discharge temperature switch. Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 50YDS038 Full Load With FV4005 Cooling - EAT 80/67°F...
Page 26
See performance correction tables for operating conditions other than those listed above. “-” HWG operation is limited by a discharge temperature switch. Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 50YDS049 Full Load With FV4006 Cooling - EAT 80/67°F...
Page 28
See performance correction tables for operating conditions other than those listed above. “-” HWG operation is limited by a discharge temperature switch. Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 50YDS064 Full Load With FV4006 Cooling - EAT 80/67°F...
All units have spring compressor mountings, TXV expansion devices, weather resistant cabinet, and 1/2” [12.2mm] & 3/4” [19.1mm] electrical knockouts. Hot Water Generator with factory installed hot gas service ports. Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 Copeland UltraTech Two-Stage Scroll 104 [2.95]...
109.0 28.9 169.0 Rated Voltage of 208/230/60/1 HACR circuit breaker in USA only Wire length based on one way measurement with 2% voltage drop Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 External Total Pump Pump Unit 14.7...
CXM board. A wire nut connection is required between the compressor solenoid valve and N.I.M. 2. Y2 connection on N.I.M. is not used for single stage units. Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 Indoor & Outdoor Split Geothermal Comfort Systems...
DIP switch 2: Stage 2 Selection - provides selection of whether compressor has an “on” delay. If set to stage Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 CXM Controls 2, the compressor will have a 3 second delay before energizing.
Page 43
The compressor is on in the heating mode and the FP2 sensor is colder than the FP1 sensor. Swapped FP1/FP2 thermistor code = 9. Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 Indoor & Outdoor Split...
CFM Adjust: Nom Fan Motor Type - HP ECM - 1/2 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 Indoor Coil Selection - GT-PX (50YDS) Puron® Geothermal Split System Geothermal split system heat pumps are rated in the ARI directory with a specifi...
Page 50
• If life expectancy of indoor coil (and associated components - fan, cabinet, etc.) is less than 7-10 years, indoor section should be replaced. Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 Equipment Selection...
fi eld connections. A thread by sweat fi tting shall be provided for connection to the water heater. All water piping shall be insulated to prevent condensation at low liquid temperatures. Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 Two-Stage Indoor Split Puron Systems...
Page 52
Air coil con nec tions shall be made through brass backseating service valves with built-in Schrader ports. Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 GT-GS Indoor Split (50YCS) Series Electrical CXM Control - A microprocessor-based compressor controller (CXM) shall be provided to monitor and control unit operation.
Page 53
Supply and return water connections shall be 1-1/4" MPT fi ttings. All water piping shall be insulated to prevent con den sa tion at low liquid temperatures. Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 R22 Systems...
Hose clamps shall be used to connect the hose to the brass elbows and Flow Controller. Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05 Cooling TXV Kit (fi eld installed) - R-22 GT-GS & GT-S units only A cooling ther mo stat ic expansion valve kit shall be provided to be fi...
Page 56
Fax: 405-745-6620 Carrier works continually to improve its products. As a result, the design and specifi cations of each product at the time for order may be changed without notice and may not be as described herein. Please contact Carrier’s Customer Service Department at 1-405-745-2920 for specifi c information on the current design and spec i fi ca tions.