Danfoss Metasys N2 Operating Instructions Manual page 7

Hide thumbs Also See for Metasys N2:
Table of Contents

Advertisement

Instructions
2.1.7 Analog Input Commands (Acknowledged)
2
2
VLT
Response
ACK
ACK
ACK
ACK
ACK
ACK
ACK
ACK
ACK
ACK
ACK
ACK
ACK
ACK
ACK, no
action
ACK, no
action
ACK, no
action
6
Command Subcom-
Region
mand
1
-
1
1
-
1
1
-
1
1
-
1
1
-
1
1
-
1
1
-
1
1
-
1
2
-
1
2
-
1
2
-
1
2
-
1
2
-
1
2
-
1
7
2
1
7
3
1
7
7
1
MG.11.G2.02 - VLT
®
VLT
Metasys
NPA Object
Attribute
Attribute Message Type
no.
No.
0-23
1
Byte
0-23
2
Byte
0-23
3
Float
0-23
8
Float
0-23
9
Float
0-23
10
Float
0-23
11
Float
0-23
12
Float
0-23
1
Byte
0-23
8
Float
0-23
9
Float
0-23
10
Float
0-23
11
Float
0-23
12
Float
0-23
-
Float
0-23
-
-
0-23
-
-
®
is a registered Danfoss trademark
Comments
Read Analog
Read Object Configuration attribute
Input
associated with each individual point
1)
Read Analog
Read Object Status attribute
Input
associated with each individual point
Read Analog
2)
Read Analog Input Value attribute
Input
associated with each individual point
Read Analog
Read Low Alarm attribute associated
Input
with each individual point
Read Analog
Read Low Warning attribute associ-
Input
ated with each individual point
Read Analog
Read High Warning attribute associ-
Input
ated with each individual point
Read Analog
Read High Alarm attribute associated
Input
with each individual point
Read Analog
Read Differential attribute associated
Input
with each individual point
Write to Object Configuration attrib-
Write Analog
ute associated with each individual
Input
point
Write Analog
Write to Low Alarm Limit attribute
Input
associated with each individual point
Write Analog
Write to Low Warning Limit attribute
Input
associated with each individual point
Write Analog
Write to High Warning Limitattribute
Input
associated with each individual point
Write Analog
Write to High Alarm Limit attribute
Input
associated with each individual point
Write Analog
Write to Differential attribute associ-
Input
ated with each individual point
Analog inputs are "outputs" from the
Override
frequency converter and should not
Analog inputs
be written over by the network
controller
Analog inputs are "outputs" from the
Override
frequency converter and should not
Analog Release
be written over by the network
controller
Write Analog
Optional command for slave devices.
Input Attrib-
Only used for N2
utes
commissioning purposes

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Metasys N2 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

This manual is also suitable for:

Vlt hvac drive fc 102Vlt aqua drive fc 202

Table of Contents

Save PDF