2.1.11 Binary Input (BI) Commands (Acknowledged)
2
2
VLT
Response
ACK
ACK
ACK
ACK, no
action
ACK, no
action
ACK, no
action
ACK, no
action
2.1.12 Binary Input (BI) Commands (Not Acknowledged)
VLT
Response
NAK
NAK
NAK
10
Command
Subcom-
Region NPA Object no. Attribute No.
mand
1
-
2
1
-
2
2
-
2
7
2
2
7
3
2
7
7
2
7
8
2
Command
Region
NPA Object
no.
2
2
0-135
2
2
0-135
2
2
0-135
MG.11.G2.02 - VLT
®
VLT
Metasys
0-135
1
0-135
2
0-135
1
0-135
-
0-135
-
0-135
-
0-135
-
Attribute No.
Attribute Message Type
2
Byte
Write Binary
3
Integer
Write Binary
4
Integer3
Write Binary
2
®
is a registered Danfoss trademark
Attribute Message Type
Byte
Read Binary
Read Object Configuration
Input
attribute associated with
each individual point
Byte
Read Binary
Read Object Status attribute
Input
associated with each individ-
Byte
Write Binary
Write to Object Configuration
Input
attribute associated with
each individual point
Byte(0/1) Override Binary
Binary inputs are "outputs"
Input
from the frequency converter
and should not be written
over by the network control-
ler. (Status word, Warnings,
-
OverrideRe-
Binary inputs are "outputs"
lease
from the drive and should
not be written over by the
network controller. (Status
word, Warnings and Alarms)
-
Write Binary
Optional command for slave
Input
devices. Only Attributes used
for N2 commissioning
purposes. Not to be
implemented at this time
-
Read Binary
Optional command for Attrib-
Input
utes slave devices. Only used
for N2 commissioning
purposes. Not to be
implemented at this time
Error
Code
11
1
Object Status not writeable
Input
1
Write Debouncing Value in msec
11
Input
attribute associated with each
individual point.(JCI use only)
1
Write Accumulator value attrib-
11
Input
ute associated with each individ-
ual point (JCI use only)
Comments
ual point
and Alarms)
Comments