Instructions
2.2.2 Scaling of Bus Reference and Feedback
Reference/
Scaling
feedback
20%
20 * 16384/100
50%
50 * 16384/100
100 *
100%
16384/100
200 *
200%
16384/100
-100 *
-100%
16384/100
-200 *
-200%
16384/100
Table 2.1: Reference/feedback values
The reference/feedback value is the percentage of the range
of parameter 3-02 and 3-03. Values within the ranges 100% to
200% and -200% to -100% applies only to the reference. The
Float representation of the value 200% must be limited to
maximum 32767 and minimum -32768.
2.2.3 Status Update Request
A Status Update Request will cause the drive to report its
current operating status. The status codes, descriptions and
associated alarms are shown in the chart below.
The Device Status Code consists of two parts. The Least Signif-
icant Byte, (LSB) of the hex number is the Alarm Number. The
Most Significant Byte (MSB) indicates if the alarm is a normal
trip (01) that can be reset automatically or manually, or if the
alarm is a trip lock (02) requiring cycling power to the drive.
®
VLT
Metasys
Float
IEEX hex
3276.8
454C CCCD
8192
4600 0000
16384
4680 0000
32767
46FF FE00
-16384
C680 0000
-32768
C700 0000
®
MG.11.G2.02 - VLT
is a registered Danfoss trademark
Status codes with associated alarms and descriptions
Device Status
Alarm
Code1
No.
0x0000
-
0x0102
2
0x0204
4
0x0107
7
0x0108
8
0x0109
9
0x010A
10
0x010B
11
0x010C
12
0x020D
13
0x020E
14
0x020F
15
0x0210
16
0x0111
17
0x0112
18
0x0116
22
0x021D
29
Heat sink temperature to high (Trip
0x011E
30
0x011F
31
0x0120
32
0x0122
34
0x0225
37
0x013C
60
0x0263
99
Read/write notes
A write command to an ADF (Internal Floating Point) or BD
(Internal Byte) point type will be stored in the drive's EEPROM.
NOTE
If write command is issued to an overridden point, the
new value will not be stored in the drive's EEPROM.
Description
Device OK
Live zero error
Phase fault (Trip lock)
Over voltage
Under voltage
Inverter overloaded
Motor overloaded
Motor thermistor
Current limit
Over current (Trip lock)
Earth fault (Trip lock)
Switch mode fault (Trip lock)
Short circuit (Trip lock)
Standard bus time out
HPFB time out
Auto optimization not OK
lock)
Motor phase U missing
Motor phase V missing
Motor phase W missing
Profibus communication error
Inverter fault (Trip lock)
Safety interlock
Unknown fault (Trip lock)
15
2
2