Binary Inputs (Bi) - Danfoss Metasys N2 Operating Instructions Manual

Hide thumbs Also See for Metasys N2:
Table of Contents

Advertisement

Appendix

3.1.2 Binary Inputs (BI)

NPA
0
1
2
3
4
5
6
7
8
9
10
11
12
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
®
VLT
Metasys
Unit
Description
15
Timers Status
14
Current Status
13
Voltage Status
12
Inverter Status
11
Running Status
10
Frequency Status
9
Control Status
8
Reference Status
7
Warning Status
3
Tripped Status
2
Drive Enabled Status
1
Drive Ready Status
0
Drive Controller Status
31
Reserved
30
Reserved
29
Unused
28
Unused
27
Voltage Limit
26
Low Temperature
25
Current Limit
24
Mains Failure
23
24V Supply Low
22
Fieldbus Fault
21
Speed Limit
20
Brake IGBT
19
Brake Resistor
18
Brake Overload
17
10V low
16
Live Zero Error
15
No Motor
14
Mains Phase Loss
13
DC Voltage High
12
DC Voltage Low
11
DC Overvoltage
10
DC Undervoltage
9
Inverter Overload
8
Motor ETR Overload
Motor Thermal
7
Overload
6
Torque Limit
5
Over Current
4
Ctrl. Word Timeout
3
Ctrl. Card Temp.
2
Earth Fault
1
Pwr. Card Temp
0
Brake Check
®
MG.11.G2.02 - VLT
is a registered Danfoss trademark
Range
0=OK, 1=Limit
0=OK, 1=Limit
0=OK, 1=Limit
0=OK, 1 =Stall, Auto-start
0=Not Running, 1=Running
0=Out of Range, 1=In Range
0=Local, 1= Bus
0=Not on Ref., 1=On Ref.
0=No Warning , 1= Warning
0=No Trip , 1=Tripped
0=Not Enabled , 1=Enabled
0=Not Ready, 1=Ready
0=Not Ready, 1=Ready
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK , 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK, 1=Warning
0=OK,1=Warning
0=OK1=Warning
FC Par. Number
Par. 16-03 Status Word
Par. 16-92 Warning Word