Technical specifications
8.5 SCALANCE M876-4 (NAM)
 
Digital input
Digital output
Permitted ambient conditions
Ambient temperature
 
 
Relative humidity
Design, dimensions and weight
Module format
Degree of protection
Weight
Dimensions (W x H x D)
Installation options
92
M876-4 (NAM)
Quantity
1
Design
Terminal block, 2-pin
Properties
Rated voltage 24 VDC Safety Extra Low Voltage
(SELV)
For state "1": 10 to 30 VDC
For state "0": -30 to 3 VDC
Maximum input current 8 mA
Cables should be routed in pairs
Maximum cable length < 30 m
Inputs isolated from electronics.
Quantity
1
Design
Terminal block, 2-pin
Properties
Rated voltage 24 VDC Safety Extra Low Voltage
(SELV)
Relay, internally not current limited
Maximum current carrying capacity 1 A
Cables should be routed in pairs
Maximum cable length < 30 m
Output isolated from electronics
During operation
Vertical mounting position
Horizontal mounting position:
During storage
-40 ℃ to +70 ℃
During transporta‐
-40 ℃ to +70 ℃
tion
During operation
≤ 95% at 25 °C, no condensation
Compact module S7-1500
IP20
290 g
34.8 x 147 x 134.7 mm
Operating Instructions, 02/2023, C79000-G8976-C331-12
Without air flow and with lateral clearance of
5 cm to the neighboring device:
-20 °C ... +60 °C
Without clearance at the side and an air flow of
0.5 m/s (only with the "LTE only" mode)
-20 ℃ to +70 ℃
-20 °C ... +50 °C
Mounting on a DIN rail
Installation on S7-300 mounting rail
Installation on S7-1500 mounting rail
Wall mounting
Mounting on a pedestal