The settings are made by using the keypad and the display on the meter:
1. Press for two seconds
2. Press repeatedly
until the display shows "Set".
- Press
to confirm.
3. Press repeatedly
until the display shows "RS-485".
- Press
to confirm.
4. Press repeatedly
until the display shows "Prot".
- Press
to access.
- Press
to enable the change in the value.
- Press repeatedly
until the display shows "Modbus".
- Press
to confirm the change.
- Press for two seconds
5. Press repeatedly
until the display shows "Baud".
- Press
to access.
- Press
to enable the change in the value.
- Press repeatedly
and select 19200.
- Press
to confirm the change.
- Press for two seconds
6. Press repeatedly
until the display shows "Address".
- Press
to access.
- Press
to enable the change in the value.
- Press repeatedly
and select 1.
- Press
to confirm the change.
- Press for two seconds
7. Press repeatedly
until the display shows "Parity".
- Press
to access.
- Press
to enable the change in the value.
- Press repeatedly
and select even.
- Press
to confirm the change.
- 89 -
to access the setup menu of the meter.
to return to the RS485 menu.
to return to the RS485 menu.
to return to the RS485 menu.