Test run instructions
Set the air conditioner to COOL mode.
For the indoor unit
Ensure the controller buttons work properly.
Double check to see if the room temperature is being registered correctly.
Ensure the indicators on the controller work properly.
Ensure the manual button on the indoor unit works properly.
Check the drain system is unimpeded and draining properly.
Ensure there is no vibration or abnormal noise during operation.
For the outdoor unit
Check for refrigerant leaks
Ensure there is no vibration or abnormal noise during operation.
Ensure the noise generated by the unit will not disturb neighbours or pose a safety hazard.
Drainage test
Ensure the drainpipe flows smoothly, for new builds perform this test before finishing the ceiling.
Remove the test cover, add 2 L of water to the tank though the attached tube.
Turn on the main power switch and run the air conditioner in COOL mode.
Listen to the sound of the drain pump to see if it makes any unusual noises.
Check to see water is discharged, it may take up to one minute.
Make sure there are no leaks in any of the piping.
Stop the air conditioner. Turn off the main power switch and reinstall the test cover.