Test run instructions
Set the air conditioner to COOL mode.
For the indoor unit
•
Ensure the controller buttons work properly.
•
Double check to see if the room temperature is being registered correctly.
•
Ensure the indicators on the controller work properly.
•
Ensure the manual button on the indoor unit works properly.
•
Check the drain system is unimpeded and draining properly.
•
Ensure there is no vibration or abnormal noise during operation.
For the outdoor unit
•
Check for refrigerant leaks
•
Ensure there is no vibration or abnormal noise during operation.
•
Ensure the noise generated by the unit will not disturb neighbours or pose a safety hazard.
Drainage test
•
Ensure the drainpipe flows smoothly, for new builds perform this test before finishing the ceiling.
•
Remove the test cover, add 2 L of water to the tank though the attached tube.
•
Turn on the main power switch and run the air conditioner in COOL mode.
•
Listen to the sound of the drain pump to see if it makes any unusual noises.
•
Check to see water is discharged, it may take up to one minute.
•
Make sure there are no leaks in any of the piping.
•
Stop the air conditioner. Turn off the main power switch and reinstall the test cover.