General Specifications
Attribute
Terminal base screw torque
Module location
Indicators, network status
Indicators, module status
Indicators, input status
POINTBus™ current, max
Power dissipation @ 28.8V DC, max
Thermal dissipation @ 28.8V DC, max
Isolation voltage
Field power supply voltage, nom
Field power voltage range
Dimensions, HxWxD, approx.
(2) (3)
Wiring category
Wire size
Weight, approx.
Enclosure type rating
Keyswitch position
North American temp code
UKEX/ATEX temp code
IECEx temp code
(1) IEC 3 24V DC input compliant.
(2) Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
(3) Use this conductor category information for planning conductor routing as described in the appropriate System Level Installation Manual.
Environmental Specifications
Attribute
Temperature, operating
Temperature, surrounding air, max
Temperature, nonoperating
Relative humidity
Vibration
Shock, operating
Shock, nonoperating
Emissions
14
Value
0.8 N•m (7 lb•in)
1734-TB or 1734-TBS wiring base assembly
1 green/red, logic side
1 green/red, logic side
1734-IB2 – 2 yellow, logic side
1734-IB4, 1734-IB4K – 4 yellow, logic side
1734-IB8, 1734-IB8K – 8 yellow, logic side
75 mA @ 5V DC
1734-IB2 – 0.7 W
1734-IB4, 1734-IB4K – 1.0 W
1734-IB8, 1734-IB8K – 1.6 W
1734-IB2 – 2.4 BTU/hr
1734-IB4, 1734-IB4K – 3.4 BTU/hr
1734-IB8, 1734-IB8K – 5.5 BTU/hr
50V (continuous), Reinforced Insulation Type
Tested @ 2500V DC for 60 s, field-side to system
24V DC
10...28.8V DC
56 x 12 x 75.5 mm
(2.2 x 0.47 x 2.97 in.)
1 – on signal ports
Determined by installed terminal block.
1734-IB2 – 30.9 g (1.09 oz)
1734-IB4, 1734-IB4K – 31.8 g (1.12 oz)
1734-IB8, 1734-IB8K – 32.3 g (1.14 oz)
None (open-style)
1
T4A
T4
T4
Value
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 °C ≤ Ta ≤ +55 °C (-4 °F ≤ Ta ≤ +131 °F)
55 °C (131 °F)
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40...+85 °C (-40...+185 °F)
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat):
5...95% noncondensing
IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10...500 Hz
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
IEC 61000-6-4