The unit is designed for indoor application with the ambient temperature ranging from +1 °C up to +40 °C and relative humidity up to 80 %.
In order to prevent condensation on the internal walls of the units, it is necessary that the surface temperature of the casing is 2-3 °C higher
than the dew point temperature of the transported air.
The unit is rated as a Class I electrical appliance.
Hazardous parts access and water ingress protection rating:
•
IP22 for the unit connected to the air ducts
•
IP44 for the unit motors
The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.
Maximum unit power (without a heater) [W]
Maximum unit current (without a heater) [A]
Sound pressure level at 3 m distance [dBA]
Filter:
700
903
153
www.ventilation-system.com
Parameter
Unit voltage [V/50 (60) Hz]
Maximum heater power [W]
Maximum unit power [W]
Maximum heater current [A]
Maximum unit current [A]
Maximum flow rate [m
Transported air temperature [°С]
Casing material
Connected air duct diameter [mm]
Heat recovery efficiency [%]
Heat exchanger type
Heat exchanger material
OVERALL DIMENSIONS OF UNITS [MM]
TECHNICAL DATA
VUTR 200 V2 EC
/h]
3
RPM [min
]
-1
Insulation
extract
supply
Weight [kg]
SEC class
347
510
TECHNICAL DATA
1~ 230
118
-
118
1.0
-
1.0
270
1800
28
-25...+40
painted steel
20 mm mineral wool
G4
G4, F7
125
47
from 75 up to 92
rotary
aluminium
А
(Top view)
598
ø125
141
124
144
600
VUTR 200 V2E
700
818
3.0
4.0
48
95
139
113
95
5