Supply voltage, 50 (60) Hz [V]
Nominal power consumption [W]
Current [A]
Maximum air flow [m
RPM, min
Sound pressure level at 3 m distance [dBA]
Transported air temperature [°C]
Casing material
Insulation
Extract filter
Supply filter
Connected air duct diameter [mm]
Weight [kg]
Heat recovery efficiency
Heat exchanger type
Heat exchanger material
www.ventilation-system.com
MODEL
/h]
3
-1
TECHNICAL DATA
VUT 160 PB EC
VUT 250 PB EC
50
0.4
190
3770
26
from -25 up to +40
40 mm mineral wool
40 mm mineral wool
Ø 125
48
from 82 up to 94 %
from 80 up to 98 %
TECHNICAL DATA
VUT 350 PB EC
1~ 220 – 240
101
170
0.8
1.3
270
410
4480
3200
28
34
aluzinc steel
40 mm mineral wool
G4
F7
Ø 125
Ø 160
48
70
from 80 up to 91 %
counter-flow
aluminium
5