Technical Data - Vents DVUT 300 HB EC User Manual

Single-room heat recovery air handling unit
Hide thumbs Also See for DVUT 300 HB EC:
Table of Contents

Advertisement

TECHNICAL DATA

The unit is designed for indoor application with the ambient temperature ranging from +1 °C up to +40 °C and relative humidity up to
60 % without condensation. In cold, damp rooms, there is a possibility of freezing or condensation inside and outside the casing.
In order to prevent condensation on the internal walls of the unit, it is necessary that the surface temperature of the casing is 2-3 °C above
the dew point temperature of the transported air.
The unit should be operated continuously, and in cases where ventilation is not necessary, reduce the air flow of the fans to a
minimum (20%). This will ensure a favorable indoor climate and reduce the amount of condensation inside the unit, which can damage
electronic components. Never use the unit for dehumidification, for example, of new buildings.
The unit is rated as a Class I electrical appliance.
Hazardous parts access and water ingress protection rating:
IP20 for the unit connected to the air ducts.
IP44 for the unit motors.
The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.
Model
Power supply voltage, 50(60) Hz [V]
Unit power consumption excl. electric heater [W]
Preheater power consumption [W]
Reheater power consumption [W]
Maximum unit current excl. electric heater [A]
Maximum unit current incl. electric heater(s) [A]
Maximum air flow [m
3
/h]
Noise level, 1 m [dBA]
Noise level, 3 m [dBA]
Transported air temperature [˚C]
Casing material
Insulation
Extract filter
Supply filter
Optional supply filter: material/size/filtration rate
Connected duct diameter [mm]
Weight [kg]
Heat recovery efficiency [%]
Heat exchanger type
Heat exchanger material
SEC class
Units without a drain pump are designed to operate in an electrical supply network with a frequency of 50(60) Hz,
with a drain pump — 50 Hz only.
www.ventilation-system.com
125
-
1400
1400
-
-
1400
-
7
13.1
320
200
138±3% 139±3% 140±3% 136±3% 137±3% 138±3% 191±3% 193±3% 194±3%
78-92
polystyrene
1~230
-
1400
1400
-
-
1400
0.9
-
7
13.1
33
23
-25...+40
painted steel
40 mm mineral wool
G4 x 2
G4 + F8
H11+ F8
200
73-89
counter-flow
enthalpy
A
230
-
1400
1400
-
-
2800
1.7
-
7.8
20
580
34
24
250
75-94
polystyrene
5

Advertisement

Table of Contents
loading

Table of Contents