6

TECHNICAL DATA

The unit is designed for indoor application with the ambient temperature ranging from +1 °C up to + 40 °C and relative humidity
up to 80 %.
Hazardous parts access and water ingress protection rating:
• IP44 for the unit motors
• IP22 for the assembled unit connected to the air ducts
The unit design is constantly being improved, so some models can slightly differ from those ones described in this manual.
Unit voltage [V /50–60 Hz]
Maximum unit power [W]
Maximum unit current [A]
Maximum air capacity [m
RPM
Sound pressure level at 3 m distance [dB(A)]
Maximum transported air temperature [°C]
Casing material
Insulation
Extract filter
Supply filter
Connected air duct diameter [mm]
Weight [kg]
Heat recovery efficiency
Heat exchanger type
Heat exchanger material
Model
VUT 160 PB EC A11
VUT 350 PB EC A11
Technical data
/h]
3
Ø16
A
A2
A1
ØD
A
A1
A2
B
125
1004 1104 1072
754
160
1135 1234 1202 1044 1112
VUT 160 PB EC A11
50
0,4
190
3770
26
Ø125
48
from 82 to 94 %
Ø10,2
8 holes
Dimensions [mm]
B1
B2
B3
H
H1
822
480
410
320
361
680
610
320
363
VUT 350 PB EC A11
1~ 230
170
1,3
410
3200
34
from -25 to +60
aluzinc steel
40 mm mineral wool
G4
F7
Ø160
70
from 80 to 91 %
counter-flow
aluminium
L5
L
L2
L2
L1
L6
L
L1
L2
L3
L4
386
293
245
31
128
555
417
345
40
119
L5
L6
123
216
144
282