- Check the box for Enable Syneto shutdown
- In the section Infrastructure connectors, click on the Add Row button. You will connect Netman 208
to the ESXi host.
- Enter the following:
ESXi Hypervisor
Username
Password
- In the section Actions, click on the Add Row button. You will define the action to take on the ESXi
host.
- Enter the following:
Action: Shutdown host
Condition:
Condition duration
(minutes):
The ip address of your ESXi host or Vcenter
The username you created for power management (eg: ups)
The username you created for power management (eg: ups)
Shutdown the host
Power fail: When the UPS detects a main failure, the configured
condition duration time(sec) will begin to countdown. Once the
timer has elapsed the selected action will start. If the main returns
within this time, then the action will be cancelled.
Autonomy less: When the calculated battery autonomy of the
UPS falls below the configured condition duration time(sec) the
selected action will start. If main returns within this time, then the
action will be cancelled.
The duration that the selected condition (Power fail or Autonomy
less) must be active for before the selected action starts.
We recommend at least 15 minutes.