Page 1
The Click 110 is used to report vehicle data to a MIDAS outstation when used with Wavetronix SmartSensors. This card plugs directly into an outstation and reports four channels of detection. Because the Click 110 has two independent serial buses, it can be configured without interfering with data reporting.
LEDs The faceplate of the Click 110 has four banks of LEDs. The top bank is used for detection indication, the second bank for fault indication, the third for menu indication, and the fourth for menu indication as well as operation states.
DIP switches Just behind the faceplate of the Click 110, on the circuit board, is a set of DIP switches. These switches are used to configure the Click 110 in Hardware mode. All settings, with the exception of Outstation mode and disabling fault latching, are also configurable via Software mode (front panel menu, or Click Supervisor).
Page 4
Click 110 pinout with Peek outstation Description Description Channel 1 fault, normally closed Channel 1, normally closed Channel 1 common No connection Channel 1 fault common Channel 1, normally open Master fault, normally closed No connection No connection No connection...
Page 5
Click 110 pinout with Siemens outstation Description Description Channel 1 fault, normally open Channel 1, normally closed Channel 1 common No connection Channel 1 fault common Channel 1, normally open Master fault, normally open No connection No connection No connection...
Preparing the SmartSensor In addition to wiring the SmartSensor to the Click 110, you must also make sure that the SmartSensor is configured correctly. Because the Click 110 device receives serial datagrams from the sensor, the sensor must be configured to report data properly for each application.
DIP switches, as shown in the figure below. The Click 110 features three DIP switches labeled S1, S2, and S3 on the label and in the figure above. (The fourth switch, labeled S4, is currently not used.) Each DIP switch is used to configure one or two different settings, for a...
Page 9
Because the Click 110 has four output channels, only four input datagram channels, received from the sensor, can be output by each device. (If you need more than four channels, consider using multiple devices.) As shown in the table below, the outputs are mapped sequentially—that is, they can only be mapped in numerically ordered groups...
6 on the S3 DIP switch to tell the Click 110 with which outstation it is going to be used. If S3:6 is off (down), the Click 110 is set to work with a Peek brand outstation. If S3:6 is on (up), the Click 110 is set to work with a Siemens brand outstation.
Menu mode. This section will cover how to use these features and the menu to configure the Click 110. The lower bank of LEDs will be referred to as Level 1 and is used is selecting menu options. The upper bank will be referred to as Level 2 and is used in configuring the menu options.
Page 12
Front panel menu options The following figure documents the menu and configuration options available from the front panel menu. This label is also printed on the side of the Click 110 (on the opposite side from the DIP switches). WX-501-0517 • 05.22...
Page 13
As mentioned earlier, the Click 110 device receives serial datagrams from a SmartSensor. These datagrams can contain many channels of detection data. Because the Click 110 has four output channels, only four input datagram channels, received from the sensor, can be output by each device. (If you need more than four channels, consider using multiple devices.) As shown in the table below, the outputs are mapped sequentially—that is, they can only...
Page 14
As each baud rate is attempted, the Level 2 LEDs will sequence with a single LED illuminated from LED 1–4. If the Click 110 is successful in communicating with a SmartSensor, it will display the baud rate found, using the same Level 2 LED system used in selecting the baud rate (covered in the Baud Rate section of this document and the table below).
Page 15
set to Hardware mode), the Level 2 LED configuration options for that bus will not be displayed (the LED option will never come on). If both RS-485 buses are configured using the DIP switches, the Level 1 LED menu option for autobaud will not be displayed (the green LED option will never come on).
Page 16
Level 1 LEDs Channel Enable All off (default) Channel 4 on Channel 3 on Channels 3 and 4 on Channel 2 on Channels 2 and 4 on Channels 2 and 3 on Channels 2, 3, and 4 on Level 2 LEDs Channel 1 on Channels 1 and 4 on Channels 1 and 3 on...
After the Click 110 has reset to factory defaults, it will check the DIP switches; if any of them are set to Hardware mode, it will apply those settings to the parameter in question. If resetting to factory defaults doesn’t change certain settings the way you expected it to, check the DIP switches to see if they are causing settings to be changed to something other than the default.
Page 18
The Click 110 can be configured using the Expert driver (see the figure below). After you have made configuration changes on the driver and saved it to the Click device, the word “current” will appear after it to indicate the driver is currently loaded onto the device.
Page 19
Firmware Version Shows the version of firmware your device currently has installed. If Click Supervisor detects a discrepancy between this version and the most current version it currently has access to, you will be prompted to upgrade when you connect to the device. This information cannot be changed. Subnet ID Shows the subnet ID number.
Need help?
Do you have a question about the Click 110 and is the answer not in the manual?
Questions and answers