Setting Parameters For The Backfeed Protection Card - Huawei UPS5000-H-400K-NT User Manual

100 kva power module
Hide thumbs Also See for UPS5000-H-400K-NT:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Module)
When an ambient T/H sensor is used as a battery temperature sensor, set the DIP
switch to a value in the range of 16 to 28 to monitor the battery temperature.
Table 5-2 DIP switch address mapping (battery temperature sensor)
No
.
6
5
4
3
2
1
Step 2 Set UI parameters.
The address set on the software must be the same as the address set on the DIP
switch. Otherwise, the communication fails.
----End

5.1.3.3 Setting Parameters for the Backfeed Protection Card

Prerequisites
A backfeed protection card is installed.
Issue 07 (2023-03-20)
DIP switch settings on battery temperature sensors
RS485 Address
16
17
18
19
0
0
0
0
1
1
1
1
0
0
0
0
0
0
0
0
0
0
1
1
0
1
0
1
NO TICE
The DIP switch address of an ambient T/H sensor ranges from 32 to 44.
LCD: Choose System Info > Settings > Comm. Settings > Amb. T/H Sensor,
and set Start address and Quantity.
WebUI: Choose System Settings > Comm. Settings > Amb. T/H Sensor, and
set Start address and Quantity.
When an ambient T/H sensor is used as a battery temperature sensor, the DIP
switch address ranges from 16 to 28.
LCD: Choose System Info > Settings > Comm. Settings > Batt Temp Sensor,
and set Start address and Quantity.
WebUI: Choose System Settings > Comm. Settings > Batt Temp Sensor, and
set Start address and Quantity.
Copyright © Huawei Digital Power Technologies Co., Ltd.
20
21
22
23
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
1
1
0
1
0
1
5 Single UPS Commissioning
24
25
26
27
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
0
0
1
1
0
1
0
1
28
0
1
1
1
0
0
228