Esserbus ® Transponder For Univario (Part No. 808623.10) - Honeywell ESSER FACP Technical Information

Table of Contents

Advertisement

Periphery components for ESSER FACP
12.2 esserbus
®
The transponder enables the connection of max. 2 industrial detectors of the UniVario product family as
components of the loop.
These detectors are supplied with energy via the 9 V DC group voltage input. For meeting the standard
requirements of monitoring, an EOL-UV terminal element is connected to the detector base of the UniVario
detector. Der Koppler benötigt eine externe Spannungsversorgung. An optional Voltage Converter
(Part No. 781336) is also required for 12 V DC operation.
Furthermore, two optionally monitored relay outputs are available.
Fig. 48: esserbus
®
transponder for UniVario
Specifications
Loop
Rated voltage
Current consumption
External power supply
Operating voltage
Current consumption
Quiescent current
Input
Current consumption
Length of connection cable
Monitoring
Relays
Contact rating
Monitoring
Ambient temperature
Storage temperature
Rel. humidity
Protection rating
Weight
Dimensions (w x h x d)
Specification
VdS approval
Declaration of Performance (808623.10)
For further information and accessories refer to product catalogue and documentation of the devices.
80
transponder for UniVario (Part No. 808623.10)
Features
Suitable for connecting industrial detectors of the UniVario product
family
Integrated loop isolator
Loop monitoring acc. EN 54-13
: 8 V DC ... 42 V DC
: approx. 90 µA @ 19 V DC
: 10 V DC ... 28 V DC
: max. 120 mA @ 12 V DC
: approx. 12 mA @ 12 V DC
: max. 25 mA @ 9 V DC
: max. 100 m
: EOL-UV
: 30 V DC / 20 mA
: EOL-O or 10 kΩ / ±40%
: -10 °C ... +50 °C
: -25 °C ... +75 °C
: ≤ 95% (no condensation)
: IP 40 (with housing)
: approx. 28 g
: 82 x 72 x 20 (mm)
: EN 54 - 17 : 2005 / - 18 : 2005
: G 210020
: DoP-20611130701
(808623.10.NU)
: DoP-20947130701
TI 798960.GB0 / 04.20