Check Item
Exhaust valve
Drainage
valve
Pipe
connection
Cable
connections
Micro
differential
pressure
sensor
(optional)
Issue 05 (2022-12-15)
Expected Result
There is no foreign matter in pressure
tubes. The pressure tubes show no
obvious bends.
The exhaust valve is closed.
The drainage valve is closed.
The water has been filled and air has
been exhausted.
The hose clamps and cable ties of the
condensate water pipe are reliably
secured.
The water inlet and outlet pipes are
properly installed and secured, without
leaks.
The water inlet and outlet pipes are
routed smoothly, without bends.
The drainpipe has a gradient (1:50 is
recommended).
The power voltage is the same as the
rated voltage on the nameplate of the
unit.
Cables are intact.
No open or short circuits, or incorrect
connections occur in electrical loops.
Power cables and signal cables have been
connected.
The rated values of circuit breakers are
correct.
Control cables are properly connected.
All cables, connectors, and bolts are
secured.
The cable ties are securely tightened
around the pressure inlet tube.
The pressure inlet tube is not blocked or
bent.
The micro differential pressure sensor is
secured reliably and steadily.
Cables are connected reliably and steadily.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 System Installation
Actual Result
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed