10.12 Replacing a Condensate Pump

Prerequisites
Before replacing the condensate pump, drain water from the water pan
completely.
Context
The condensate pump needs to be maintained from the air return side.
Procedure
Step 1 Tap Shutdown on the home screen of the display module.
Exercise caution because the unit is still energized after it is shut down on the
screen of the display module.
Step 2 Turn off the active power switch QF1 and standby power switch QF2.
Step 3 Remove the air filter.
Step 4 Block the water inlet pipe in the water pan to prevent condensate water from
flowing out of the water pan.
Step 5 Disconnect the condensate pump power cable terminal at the bottom of the
cabinet.
Step 6 Remove the hose clamp from the water outlet pipe using a flat-head screwdriver,
and remove the pipe.
Issue 05 (2022-12-15)
A condensate pump needs to be replaced.
A spare condensate pump of the same model is available and functional.
Tools: flat-head screwdriver, Phillips screwdriver, socket wrench