Electric Ball Valve
Figure 10-6 Electric ball valve
(1) Valve body
(4) Water valve actuator
handle
Procedure
Step 1 Tap Shutdown on the home screen of the display module.
Step 2 Open the electric control box, and turn off the active power switch QF1 and
standby power switch QF2.
Step 3 Remove the air filter on the right.
Step 4 Remove the wiring terminals connected to the actuator using a small-sized flat-
head screwdriver, and cut off the cable ties that bind the actuator cables to ensure
that the cables are separated from the unit.
Step 5 Remove the chilled water valve actuator.
1.
2.
3.
Issue 05 (2022-12-15)
Remove the actuator handle.
Insert the hex key on the handle into the hole in the front of the actuator.
Loosen the screws and remove the actuator.
NO TE
If there is interference with the water inlet pipe onsite, remove it using the short edge
of a common hex key.
Copyright © Huawei Digital Power Technologies Co., Ltd.
(2) Water valve actuator
(5) Mounting kit
10 Parts Replacement
(3) Connecting plate