FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual
Step 9 Install a new condensate pump and secure it using hose clamps.
Step 10 Connect the water pipes and secure them using hose clamps.
Step 11 Connect the power cable terminal of the condensate pump.
Step 12 Remove the blockage from the water pipe and install the air filter.
Step 13 Power on the unit, tap Start on the home screen, choose Maintenance >
Performance Maintenance, and clear the runtime of the condensate pump.
Step 14 Tap Start on the home screen and check that the smart cooling product is running
properly and no alarm is generated.
----End
10.13 Replacing a Display Module
Prerequisites
●
●
Context
Recommended tools: Phillips screwdriver (M4), ESD gloves
Procedure
Step 1 On the home screen of the display module, tap Shutdown and turn off the unit
switch in the PDF.
Exercise caution because the unit is still energized after it is shut down on the
screen of the display module.
Step 2 Replace the display module.
● Do not frequently or quickly disconnect or connect the DP cable of the display
module. Do not forcibly pull the DP cable.
● You are advised to power off the main control board (or main control module)
and then replace the display module.
1.
2.
Issue 05 (2022-12-15)
A display module needs to be replaced.
A spare display module of the same model (or BOM number) as the faulty
display module is available.
NO TICE
CA UTION
Open the front door with caution to prevent damaging the cables of the
display module.
Remove the cables from the display module.
Copyright © Huawei Digital Power Technologies Co., Ltd.
10 Parts Replacement