6.2.1.2

Error Definitions

F.F 00 00 00 01
F.F 00 00 00 04
F.F 00 00 00 08
F.F 00 00 00 10
F.F 00 00 00 20
F.F 00 00 01 00
F.F 00 00 02 00
© Landis+Gyr
Clock Invalid Error
Purpose:
Indicates an invalid time and date. This error appears after long
mains power failure when the power reserve of the clock is
exhausted
Category:
Other errors
Reset:
The error is cleared automatically when the clock is reset.
Unknown or Unsupported Extension Board Error
Purpose:
Indicates an unsupported or corrupted extension board is fitted.
Category:
Other errors
Reset:
The error is cleared automatically when the board is replaced.
Contact a Landis+Gyr service centre.
Profile(s) Checksum Error
Purpose:
Indicates a logical error on at least one profile, i.e. a checksum
error. The checksum is calculated over the whole profile area.
Category:
Other errors
Reset:
The error is cleared automatically when the checksums are cor-
rect again, e.g. with the next read/write to the profiles or reset
via communication.
Disconnector Control Unit Failure Error
Purpose:
Indicates a possible failure of the disconnector control unit.
Category:
Other errors
Reset:
The error is cleared automatically when the next successful dis-
connector operation has been made.
One or more parameter could not be restored after firmware upgrade
Purpose:
Indicates that one or more parameters could not be restored
after a firmware upgrade. The objects with parameters which
could not be restored will run on the default parameters.
Category:
Other errors
Reset:
The error is cleared automatically when the next successful
firmware upgrade has been made or can be deleted via com-
munication.
Program Memory Error
Purpose:
Indicates a checksum failure in the parameter data
Category:
Critical error
Reset:
The error is not reset automatically; the register must be cleared
via communication.
RAM Error
Purpose:
Indicates an error in the internal program memory (RAM)
Category:
Critical error
Reset:
No reset possible, the device must be replaced.