1.4.2.2 LoRa module configuration
The module can be configurated by using the Device Monitors or the OTC App.
Parameter
Power mode
Configuration Lock
Synchronize meter time
Activation type
EcoMode
Transmit interval *[Min.]
Message format**
Pulse input selection
* The actual transmission interval depends on the type of telegram and the current data rate. The transmission interval is
adjusted accordingly in order to guarantee the set battery life (Eco Mode 10 or 6 years). You can find more information in
the „Manual LoRa Module".
** For pulse input option, the telegram type „Sensus" must be selected.
1.4.2.3 Activation of the radio interface
The radio interface is deactivated by default and can be activated in one of the three following ways:
a)
NTC interface – via Elvaco OTC App; further information is available in the operating instructions of the Elvaco OTC App:
https://www.elvaco.se/Image/GetDocument/en/269/elvaco-otc-app-manual-english.pdf
b)
Optical interface – via the Sensus configuration software Device Monitor – from version 2.22; further information is
available in the operating instructions of the Device Monitor. The software can be ordered separately.
c)
Via the heat meter menu;
Press and hold the button to switch to display loop "6" (= module loop; see Chapter 3
Display in the Module Loop (Optional)). Then switch to the second loop with a short press of
the button – 6-02 – „EnA oFF" (see image).
In order to start the edit mode, you must then press the key
press once more for 2-3 seconds. As an aid, an "editing pen" symbol appears in the lower
left corner of the LCD after 2 seconds. As soon as it can be seen, you must release the
button. The display now shows „EnA on" and a black triangle in all display loops (see image).
1.4.2.4 Connection to the LoRaWAN Network
To check whether the meter has already connected to the LoRaWAN network, change from loop
6-02 to loop 6-03 by briefly pressing the button. As long as the meter is searching for the
LoRaWAN network, „LorA Pen" appears in the LCD; the time between each connection attempt is
gradually reduced to at least once a day.
As soon as the meter has connected to the LoRaWAN network, "LorA Con" appears in the LCD.
51 / 107
Possible settings
Active
Inactive
Open
Locked
on
off
OTAA
ABP
off
6 years
10 years
5 ... 1440
Standard
Sensus
Compact
JSON
Scheduled - daily redundant
Scheduled - extended
Combined heat/cooling
Choice between 0-3 pulse inputs
1080619050 / MH 4310 INT5
Factory setting
Inactive
Open
off
OTAA
EcoMode 10 years
60
Standard
0
2022_09_22 V 0001