The installation has to fulfill the requirements of the relevant norms / standards / literature (see paragraph 2.1) and the
specifications as follows:
Maximum voltage M-Bus
Minimum voltage M-Bus
Maximum ripple voltage
Maximum voltage potential
differences
1.2.3 Technical data M-Bus
Primary address
Baud rate
Connecting cable length
Number of possible read-outs
Refresh of data
1.3 Modbus RTU (optional)
The Modbus RTU Module is a galvanically isolated interface for the transmission of meter data (absolute values). It is designed
for use with PolluStat heat meter and PolluTherm F calculator to connect them to Modbus RTU network using EIA-485 channel.
1.3.1 Technical data Modbus
Connector A
Connector B
Maximum power consumption
Communication protocol
Channel
Baud rate
1.3.2 Default factory settings
Communication parameters
Update Rate Data from Meter
Modbus Slave ID*
Automatic Slave ID**
* Acceptable values: 1 ... 247
** If the automatic Slave ID is activated (set to = 1), the M-Bus address which is set in the meter is used for communication.
1.4 Wireless Interfaces
Sensus offers the following radio interfaces:
-
wireless M-Bus interface EN 13757-3, -4 (see chapter 1.4.1)
-
LoRaWAN communication interface (see chapter 1.4.2)
General information about the radio interface:
Installation of radio components between or behind heating pipes, or the presence of other bulky metallic obstacles directly
over or in front of the housing must be avoided.
The transmission quality (range, telegram processing) of radio components can be negatively influenced by instruments or
equipment with electromagnetic emissions, such as telephones (particularly LTE mobile radio standard), wi-fi routers, baby
monitors, remote control units, electric motors, etc.
In addition, the construction of the building has a strong influence on the transmission range and coverage. Furthermore, when
using installation boxes (substations) they must be equipped with non-metallic covers or doors.
The factory-setting of the clock in the meter is standard (winter) Central European Time (GMT +1). There is no automatic
changeover to daylight savings (summer) time.
The radio function is deactivated upon delivery (factory-setting). See chapter 1.4.1.3 & 1.4.2.3 regarding the activation of the
radio interface.
48 / 107
42 V
24 V
200 mV; EN 13757-2_2004; 4.3.3.6
2 V
0 (factory setting); 1 - 250 (configurable)
2400; 300
1 m
unlimited
120 s; using a power pack: 2 s
PowerSupply 12 V – 24V DC ± 10% (SELV power supply only)
Modbus Network
500 mW
Modbus RTU
EIA-485 (galvanically isolated)
1200, 2400, 4800, 9600, 14400, 19200, 38400, 56000, 57600, 115200
9600 bps, 8N1 data format (8 data bits, none parity, 1 stop bit)
600 s
1
0 (deactivated)
1080619050 / MH 4310 INT5
2022_09_22 V 0001