ADVANCED CONFIGURATION SERVICE MENUS
CONFIGURE SERVICE MENUS
The following Service Menus (SM) commonly require configuration. Please verify that
these are set for your specific application. Additional configuration may be required.
• SM 100 = Programmable or Nonprogrammable
• SM 110 = System Type
• SM 120 = Fan Control for Heating
• SM 135 = W1 Heat Output NO or NC
• SM 170 = Remote Sensors
• SM 240 = Number of Programmable Events per Day
• SM 395 = Override Duration for Programmable Operation
• SM 340 = Keypad Lock Out

SERVICE MENU ACCESS

1.
Hold lower right and lower left keys for five seconds.
2.
Press
Next
or
Go Back
button to select a Service Menu.
3.
Press ▲/ ▼ to select option.
4.
Press
Done
when complete.
Menu
Feature
100
Schedule Format
101
Daylight Savings
110
System Type
111
Outside Air Damper
Configuration
120
Fan Control (Heating)
121
Fan Speeds
134
Cool Output Configuration
135
W1 Heat Output
Configuration
170
Remote Sensor Input
171
Pipe Sensor
172
Pipe Sensor Threshold for
Cooling
173
Pipe Sensor Threshold for
Heating
© COPYRIGHT 2023 PECO, INC. ALL RIGHTS RESERVED.
Option
0 = Nonprogrammable (Default)
1 = Programmable
2 = 5-1-1 Schedule Mode
3 = 5-2 Schedule Mode
0 = Disabled (Default)
1 = Enabled (2007 US Format)
1
1 Stage Heat /1 Stage Cool (Default)
2
2 Stage Heat /1 Stage Cool
3
1 Stage Heat Only
4
1 Stage Cool Only
0 = Damper Continuous
1 = Damper Cycled with Demand (Default)
0 = OFF for Heating (Gas/Oil Heat)
1= Electric Furnace (Default)
1 = Single Speed Fan
2 = 2-Speed Fan
3 = 3-Speed Fan (Default)
0 = NC: Normally Closed Operation (Default)
1 = NO: Normally Open Operation
0 = NC: Normally Closed Operation (Default)
1 = NO: Normally Open Operation
0= No Remote Sensors (Default)
1= Remote Indoor Sensor Connected
2 = Remote Sensor Connected And Sensor
Averaging
0 = Disabled (Default)
1 = Two Pipe Operation
2 = Four Pipe Operation (use for 2-pipe with
electric heat relay)
50F to 72F (Default 60F)
75F to 90F (Default 80F)
Description
Selects the schedule format. In non-programmable mode all scheduling functions are
removed from the display.
When enabled daylight savings time follows the US 2007 format. (Begins second Sunday
of March at 2AM and ends on the first Sunday of November at 2AM.
Heat Stage 2 takes the place of this outside air damper output.
Damper output is not available when being used as a fan speed.
0: Output runs continuously when thermostat is not in System OFF Mode.
1: Output cycles with a heat or cool demand.
0: The thermostat will Not activate the fan with a heating demand.
1: The thermostat will activate the fan with heat demand.
Single Speed - White/Orange Lead
2-Speeds - White/Orange & White Brown Leads
3-Speeds - White/Orange, White/Red & White Brown Leads
Reverses the ON/OFF operation for the heat output. NC operation powers on with a
demand. NO opreation powers off with a demand and will be on with no demand unless
main power is removed from the thermostat.
Reverses the ON/OFF operation for the first stage heat output. NC operation powers on
with a demand. NO opreation powers off with a demand and will be on with no demand
unless main power is removed from the thermostat.
0: Remote temperature sensing is disabled.
1: The TW180 uses the remote sensor only for temperature sensing.
2: The TW180 averages the local and remote sensor for temperature sensing.
When using a remote sensor an open or short will turn off outputs and display either
2Ero(open) or 2Erc (closed). Fault detection settings are not used.
Enables fan coil pipe sensor operation. Connect a PECO pipe sensor or dry switch closure
for change over from Summer (cold water) to Winter (hot water) on COOL output (blue
wire). 2-pipe operation uses the COOL output for heating and cooling. Heat 1 is disabled.
4-pipe operation allows heat 1 in summer mode of operation.
Available when SM 110 = 1 or 2
Available when SM 171 = 1 or 2. Changes to Cool when pipe temp is below threshold.
Available when SM 171 = 1 or 2. Changes to Heat when pipe temp is above threshold.
4
Service Menu
Number
P/N 74150 3220-2384 REV 04
Selected
Option