Use this Quick Start Guide (QSG) in conjunction with the Tigo
Detailed installation documentation for all Tigo products is available on the tigoenergy.com
Order of Installation
Install an EI system in this order:
1. Install TS4s and the Tigo Access Point (TAP) anytime before
wiring the inverter.
2. Mount the ATS and connect it to the grid. To enable
household power pending commissioning, use the ATS
manual bypass feature described herein.
Mount Enclosure
1. Locate the ATS enclosure:
2. In a well-ventilated, easily accessible location.
3. On a flat surface against a solid wall with ≤15° tilt.
4. Sheltered from direct sunlight and precipitation.
>12in
>12in
>12in
Power Connections
Use non-fine-stranded wire with ferrules. Torque terminals to 22.5Nm.
ATS to Load and Grid
1/0 – 4/0 AWG
L1
L2
G
G
N
Whole home: to main panel
Partial home: to essential loads panel
EI Residential Solar Solution
Quick Start Guide – EI ATS 200A
EI Inverter
QSG.
Downloads
page.
3. Mount the inverter and E-Stop rapid shutdown switch.
4. Place the battery.
5. Wire communications and power connections.
You must install communications connections.
6. Commission the system.
Ambient temperature should not exceed 50°C.
5. Away from antennas or other sources of strong
electromechanical interference.
6. Above potential flooding.
≤15˚
EI Inverter to ATS
L1
L2
N
Whole home: to grid
Partial home: to main panel
Connection Points
8 – 6 AWG
L1
N
L2
• All components must be installed and maintained
• Always wear appropriate PPE and use insulated tools.
• Improper installation may cause damage not covered
Inverter communications
terminals
Manual bypass jumper
Generator start signal
terminals
Inverter AC terminals
Neutral busbar
Ground busbar
ATS to Generator (
L1
L2
N
G
N
To generator battery charger
(120V
12 – 10 AWG)
AC
by qualified personnel in accordance with applicable
electrical codes.
by the warranty.
200A service disconnect
Generator and load terminals
Grid terminals
Neutral busbar
Ground busbar
Generator battery
maintenance terminal
TSS-200A-US-G only) 4 – 1/0 AWG
L1
L2
G
N
L1
G
To generator power