Configuration Menu - Watts AERCO Benchmark 2.0 User Manual

Gas-fired boiler
Table of Contents

Advertisement

MENU & OPTION
Setup Menu
Password
Language
Unit of Temp
Comm Address
Baud Rate

Configuration Menu

Internal Setpt
Unit Type
Unit Size
Boiler Mode
Remote Signal
(If Mode = Remote Setpoint, Direct Drive or
Combination)
Bldg Ref Temp
(If Boiler Mode = Outdoor Reset)
Reset Ratio
(If Boiler Mode = Outdoor Reset)
Outdoor Sensor
System Start Tmp
(If Outdoor Sensor = Enabled)
Setpt Lo Limit
Setpt Hi Limit
Temp Hi Limit
Max Fire Rate
Pump Delay Timer
Aux Start On Dly
Failsafe Mode
mA Output
Lo Fire Timer
Setpt Limit Band (If Setpt Limiting = Enabled)
Tuning Menu
Prop Band
Integral Gain
Derivative Time
BOILER DEFAULT SETTINGS
APPENDIX E
FACTORY DEFAULT
0
English
Fahrenheit
0
9600
130°F
Boiler
1.0 MBTU
Constant Setpoint
4 – 20 mA / 1-5V
70°F
1.2
Disabled
60°F
60°F
200°F
210°F
100%
0 min
0 sec
Shutdown
Off
2 sec
5°F
70°F
1.00
0.0 min
E-1

Advertisement

Table of Contents
loading

This manual is also suitable for:

G-10-1060G-02-533

Table of Contents