Electrical Supply - Watts AERCO Benchmark 2.0 User Manual

Gas-fired boiler
Table of Contents

Advertisement

MANDATORY GAS
PRESSURE REGULATORS
(SUPPLIED BY AERCO)
2" MANUAL SHUT OFF
Figure 2.5
Gas Supply Regulator and Manual Shut-Off
Valve Location

2.5 ELECTRICAL SUPPLY

The AERCO Gas Fired Equipment Electrical
Power Wiring Guide, (GF-2060), must be
consulted in addition to the following material
before wiring to the unit is started. External AC
power connections are made to the unit inside
the power box on the front panel of the unit,
behind the removable front door (Figure 2.6).
NOTE:
All electrical conduit and hardware should
be installed so that it does not interfere with
the removal of any cover, inhibit service or
maintenance, or prevent access between
the unit and walls or another unit.
GAS SUPPLY:
SEE GF-2030 FOR
COMPLETE GAS
PIPING INSTALLATION
DETAILS
NATURAL GAS
SUPPLY
PROPANE
SUPPLY
FOR DUAL
FUEL OPTION
DIRT
TRAP
2.5.1 ELECTRICAL REQUIREMENTS
The Benchmark Boiler is available in one three
different AC power configurations:
220 Vac/1 Phase/60 Hz @ 20 amps
208 Vac/3-Phase/60 @15 amps
460 Vac/3-Phase/60 Hz @ 15 amps
Each of the above power configurations contain
a Power Box with a terminal block which
matches the configuration ordered. The three
different terminal block configurations are shown
in Figure 2.7.
required AC power connections is provided on
the front panel of each Power Box.
Each Benchmark Boiler must be connected to a
dedicated electrical circuit.
should be on the same electrical circuit as the
Benchmark Boiler. A means for disconnecting
AC power from the unit (such as a service
switch) must be installed near the unit for normal
operation and maintenance. All electrical con-
nections should be made in accordance with the
National Electrical Code and/or with any
applicable local codes.
For electrical power wiring diagrams, see the
Benchmark Electrical, Power Wiring Guide, GF-
2060
INSTALLATION
TERMINAL BLOCK
UPPER RIGHT CORNER OF FRONT PANEL
Figure 2.6
AC Input Terminal Location
A wiring diagram showing the
No other devices
2-5