Follow these recommendations for copper data cabling in high electrical noise envi-
ronments:
Data cable lengths should be as short as possible, preferably 3 m (10 ft) in
length. Copper data cables should not be used for inter-building communica-
tions.
Power and data cables should not be run in parallel for long distances, and
should be installed in separate conduits. Power and data cables should intersect
at 90° angles when necessary to reduce inductive coupling.
Shielded/screened cabling can be used when required. Care should be taken to
avoid the creation of ground loops with shielded cabling.
1.5.3

Supported Fiber Optic Cables

The following fiber optic cable types are supported under the stated conditions.
Cable Type
Wavelength (nm)
OM1 (62.5/125)
OM2 (50/125)
a
OM3 (50/125)
a
OM4 (50/125)
a
Laser optimized.
1.6

Tamper-Evident Security Seals

In compliance with the security requirements of the Federal Information Processing
Standards (FIPS140-2), FIPS-compliant tamper-evident security seals are applied to
potential access points on this device. Security seals provide evidence of unautho-
rized tampering or removal of components.
NOTICE
Worn, damaged or missing seals must be replaced immediately.
Replacement seals are available for purchase from Siemens. For more information,
contact a Siemens Sales representative.
There are three ways to determine if a security seal has been tampered with:
The seal is cut or torn
A pattern is left on the device when the top layer of the seal is removed
Residue left by the seal is visible on the device under ultra-violet light
RUGGEDCOM M2100F
Installation Manual, 01/2020, C79000-G8976-1342-06
All manuals and user guides at all-guides.com
Modal Band-
width (MHz·km)
850
200
1300
500
850
500
1300
500
850
1500
1300
500
850
3500
1300
500
1.5.3 Supported Fiber Optic Cables
Distance (m)
100Base-FX
1000Base-SX
275
2000
550
2000
550
2000
550
2000
Introduction
10GBase-SR
33
82
300
400
5

Advertisement

Table of Contents
loading

Table of Contents