Technical Data - Siemens SINAMICS G130 Function Manual

Chassis, cabinet modules
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

5.2.4

Technical data

Refer to the documentation of the corresponding built-in device or cabinet unit for technical
data relating to temperature, vibration, shock and environmental classes.
Table 5- 6
Technical data of the terminal module for option K82
Functional safety
SIL claim limit
Achievable category and
Performance Level
PFH, PFH
D 1)
PFD
2)
TM: Usage time
(mission time)
3)
Test stop
HFT
Response time when activat-
ing STO
Switch-on threshold
Switch-off threshold
PFH, PFH
: Probability of dangerous failures per hour.
1)
D
PFD: Probability of dangerous failure on demand
2)
IEC 61800-5-2 mission time TM: Usage time, defined accumulated operating duration of the PDS(SR) over its complete
3)
service life.
Safety Integrated
Function Manual, 08/2023, A5E03264275A
5.2 Control of "STO" and "SS1" via terminal module for option K82
SIL 2 according to IEC 61800-5-2
Depending on the application and the diagnostic test interval
PL d / Cat. 3 according to ISO 13849-1
Depending on the application and the diagnostic test interval
0.5 x 10
1/h according to IEC 61800-5-2 / IEC 62061
-9
0.5 x 10
1/h acc. to IEC 61511
-4
20 years
≤ 1 year
HFT = 1
100 ms additional response time to the STO response time without K82
≤ 15 V
≥ 5 V
Controlling the safety functions