Description Of Safety Integrated Functions; Preconditions For Safety Integrated Basic Functions - Siemens SINAMICS G130 Function Manual

Chassis, cabinet modules
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Description of Safety Integrated functions

Safety Integrated Basic Functions and Safety Integrated Extended Functions are described in
detail in the "SINAMICS S120 Safety Integrated Function Manual".
The "SINAMICS S120 Safety Integrated Function Manual" is available on the Internet at the
following address (https://support.industry.siemens.com/cs/ww/en/ps/13231/man).
4.1

Preconditions for Safety Integrated Basic Functions

The following prerequisites apply for operation of the Safety Integrated Basic Functions:
• For G150, S120 Cabinet Modules and S150 with control cables >30 m:
Option K82 (terminal module for controlling safety functions "Safe Torque Off" and "Safe
Stop 1")
• An activated current controller in the drive (comprising converter and motor)
• For the safe brake control:
– For G150, S120 Cabinet Modules and S150:
– For the G130 and S120 Chassis units:
Safety Integrated
Function Manual, 08/2023, A5E03264275A
Option K88 (Safe Brake Adapter 230 VAC)
Option SBA (Safe Brake Adapter)
4
31