Fci2016-U1 Periphery Board (252P); Description - Siemens FC2025 Manual

Fire alarm control panel marine application
Table of Contents

Advertisement

FS20 Marine Fire Detection Control Panel
10

FCI2016-U1 Periphery Board (252p)

Description

10.1
The periphery board (252p) FCI2016-U1 is used for fire control panels with maximum
252 initiating device addresses. The periphery board is use to provide a method for
supervising and controlling various peripheral devices, such as detectors, notification
devices, and providing power for the entire panel.
There is a detector core on the periphery board that is isolated from the rest of the
periphery board. An auxiliary output circuit (1.5 A, 24 V) provides power to remote
devices or internal modules. The integrated NAC circuit (NAC 1) provides up to
three A of power for one class A circuit or for each of two class B circuits. The
periphery board has expansion capabilities for releasing circuit with two zones, and an
additional NAC circuit (NAC 2).
The periphery board has a battery charger and battery switchover circuit for AC
outage or brownout. The battery charger is capable of charging up to 100 Ah batteries.
48
Siemens Industry, Inc.
Building Technologies Division
A6V10519176_enUS_b