Temporarily Removing Multiple Based Devices

26.2
When temporarily removing a device for the purpose of maintenance, ensure each device is
returned to its original based. The devices must not be swapped.
Mark the location of the devices to the respective base to avoid additional steps.
1. Bypass the 'Zone'
2. Remove the device from the base and insert the dummy detector if necessary.
3. Perform the tasks.
4. Re-insert the devices to the respective position.
5. Enable the 'Zone'.
6. Re-start the detector circuit.
If detectors have been swapped or missing, the following message is displayed on the
Operating Unit:
'Zone', Serial no.', 'Dev.loc' trouble'
The steps are performed when the detector circuit is enabled.

Permanently Removing Based Devices

26.3
1. Bypass the detector circuit.
2. Uninstall the devices and bases.
3. Enable the detector circuit.
4. Individually delete the devices using the Operating Unit on the control panel.
5. Connect the PC to the 'Panel'.
6. Load the configuration from the 'Panel' to the PC.
7. Remove the elements in the configuration tool.
8. Load the configuration from the PC to the 'Panel'.
9. Disconnect the PC from the 'Panel'.
10. Process is completed.