10 Supplement

10.1 Technical data

General data PLICSMOBILE T81
Materials
Ʋ Plastic housing
Ʋ Aluminium die-cast housing
Ʋ Stainless steel housing
Ʋ Cable gland
Ʋ Sealing, cable gland
Ʋ Blind plug, cable gland
Ʋ Seal between housing and housing lid Silicone SI 850 R, NBR silicone-free
Ʋ Ground terminal
Weight
Ʋ Plastic housing
Ʋ Aluminium housing
Ʋ Stainless steel housing
Power supply PLICSMOBILE T81
Operating voltage
1)
Power consumption
2)
Ʋ Power saving mode (9 V/12 V)
Ʋ Power saving mode (24 V/32 V)
Ʋ Permanent operation
Ʋ Peak power (measured value trans-
mission)
Power requirement
3)
Ʋ Measurement cycle incl. transmission 15 mWh
Sensor power supply
Ʋ Off-load voltage
Ʋ Max. current
PLICSMOBILE B81
Materials
Ʋ Aluminium housing
Ʋ Cable gland
Ʋ Sealing, cable gland
When the instrument is powered by an external voltage supply, make sure the voltage supply unit has a suf-
1)
ficient current carrying capacity. With a voltage supply <9.6 V, current peaks of up to 2 A must be expected.
The listed power specifications include the voltage supply of a HART sensor with 20 mA.
2)
The listed energy requirement includes the voltage supply of a HART sensor (VEGAPULS 61 with 4 mA (multi-
3)
drop mode) and 12 V operating voltage.
PLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit
plastic PBT (Polyester)
Aluminium die-casting AlSi10Mg, powder-coated - basis:
Polyester
316L
PA
NBR
PA
316L
approx. 1.18 kg (2.59 lbs)
approx. 1.65 kg (3.65 lbs)
approx. 3 kg (6.61 lbs)
9.6 ... 32 V DC
0.18 mW/0.3 mW
1.8 mW/3.7 mW
1.1 W
5.1 W
34 V (31 V with Ex version)
80 mA (26 mA with Ex version)
Aluminium die-casting
PA
NBR
10 Supplement