Page 3
Instructions manuals for accessories and replacement parts Tip: To ensure reliable setup and operation of your VEGACAL 63, we offer accessories and replacement parts. The associated documents are: 27720 - VEGADIS 61 30531 - Electronics module VEGACAL series 60...
List The dot set in front indicates a list with no implied sequence. à Action This arrow indicates a single action. Sequence Numbers set in front indicate successive steps in a procedure. VEGACAL 63 • 4 … 20 mA/HART two-wire...
During work on and with the device the required personal protective equipment must always be worn. 2.2 Appropriate use VEGACAL 63 is a sensor for continuous level measurement. You can find detailed information on the application range in chapter "Product description".
2.6 CE conformity This device fulfills the legal requirements of the applicable EC guidelines. By attaching the CE mark, VEGA provides a confirmation of successful testing. You can find the CE conformity declaration in the download area of www.vega.com.
Process fitting with probe Housing with electronics Housing cover, optionally available with indicating and adjustment module Fig. 1: VEGACAL 63 - rod version with plastic housing Housing cover with integrated indicating and adjustment module (optional) Housing with electronics Process fitting The type label contains the most important data for identification and...
In addition to the type label outside, you can also find the serial number on the inside of the instrument. 3.2 Principle of operation VEGACAL 63 is a level sensor with fully insulated probe for continuous Application area level measurement.
This function is generally not available for approved instruments. 3.3 Operation VEGACAL 63 can be adjusted with different adjustment media: with indicating and adjustment module with the suitable VEGA DTM in conjunction with an adjustment software according to the FDT/DTM standard, e.g. PACTware and with manufacturer-specific adjustment programs AMS™...
Page 10
Protected against solar radiation Avoiding mechanical shock and vibration Storage and transport temperature see chapter "Supplement - Storage and transport temperature Technical data - Ambient conditions" Relative humidity 20 … 85 % VEGACAL 63 • 4 … 20 mA/HART two-wire...
Rain and condensation water can thus drain off. This applies mainly to outdoor mounting as well as installation in areas where high humidity is expected (e.g. through cleaning processes) or on cooled or heated vessels. VEGACAL 63 • 4 … 20 mA/HART two-wire...
Page 12
This applies particularly to applications in non-conductive products. In cylindrical tanks, spherical tanks or other asymmetrical tank forms, nonlinear level values are generated due to the varying distance to the vessel wall. VEGACAL 63 • 4 … 20 mA/HART two-wire...
For this reason, mount the instrument at a position in the vessel where no disturbances, e.g. from filling openings, agitators, etc., can occur. This applies particularly to instrument versions with a longer probe. VEGACAL 63 • 4 … 20 mA/HART two-wire...
Page 14
To compensate the normal voltage loss due to sealing materials, you Torque with PTFE plated have to additionally use disc springs for fastening flange screws on flanges PTFE coated flanges. Tighten the screws moderately with the torque stated in the technical data. VEGACAL 63 • 4 … 20 mA/HART two-wire...
The signal conditioning instruments VEGAMET 624 and 625 as well as VEGASCAN 693 have a digital sensor recognition. When connecting VEGACAL 63, a software version from 1.92 is required with the signal conditioning instrument. For software update move under "www.vega.
1 cm (0.4 in) insulation from the ends of the individual wires Insert the cable through the cable gland into the sensor Lift the opening levers of the terminals with a screwdriver (see following illustration) VEGACAL 63 • 4 … 20 mA/HART two-wire...
12 Screw the housing cover on The electrical connection is finished. 5.3 Wiring plan, single chamber housing The following illustrations apply to the non-Ex as well as to the Ex-ia version. VEGACAL 63 • 4 … 20 mA/HART two-wire...
Page 18
Aluminium Stainless steel, investment casting Stainless steel, electro-polished Filter element for air pressure compensation of all material versions. Blind stopper with version IP 66/IP 68, 1 bar for Aluminium and stainless steel VEGACAL 63 • 4 … 20 mA/HART two-wire...
Fig. 9: Wiring plan, single chamber housing Voltage supply/Signal output 5.4 Wiring plan, double chamber housing The following illustration apply to non-Ex as well as Ex ia versions. The Exd version is described in the next subchapter. VEGACAL 63 • 4 … 20 mA/HART two-wire...
Page 20
Display I ² C 5 6 7 8 Fig. 11: Electronics compartment, double chamber housing Plug connector for VEGACONNECT (I²C interface) Internal connection cable to the connection compartment Terminals for VEGADIS 61 VEGACAL 63 • 4 … 20 mA/HART two-wire...
Page 21
Plug connector for VEGACONNECT (I²C interface) Ground terminal for connection of the cable screen Spring-loaded terminals for voltage supply Wiring plan I 2 C Fig. 13: Wiring plan, double chamber housing Voltage supply/Signal output VEGACAL 63 • 4 … 20 mA/HART two-wire...
Display I ² C 5 6 7 8 Fig. 15: Electronics compartment, double chamber housing Plug connector for VEGACONNECT (I²C interface) Internal connection cable to the connection compartment Terminals for VEGADIS 61 VEGACAL 63 • 4 … 20 mA/HART two-wire...
Page 23
Fig. 16: Connection compartment double chamber housing Ex d Spring-loaded terminals for power supply and cable screen Ground terminal for connection of the cable screen Wiring plan Fig. 17: Wiring plan double chamber housing Ex d Voltage supply/Signal output VEGACAL 63 • 4 … 20 mA/HART two-wire...
5.6 Wiring plan - version IP 66/IP 68, 1 bar Wire assignment, con- nection cable Fig. 18: Wire assignment, connection cable brown (+) and blue (-) to power supply or to the processing system Shielding VEGACAL 63 • 4 … 20 mA/HART two-wire...
Screw housing cover with inspection window tightly back on Removal is carried out in reverse order. The indicating and adjustment module is powered by the sensor, an additional connection is not necessary. VEGACAL 63 • 4 … 20 mA/HART two-wire...
Page 26
Fig. 19: Insert indicating and adjustment module Note: If you intend to retrofit the instrument with an indicating and adjustment module for continuous measured value indication, a higher cover with an inspection glass is required. VEGACAL 63 • 4 … 20 mA/HART two-wire...
The functions of the individual keys are shown in the above illustration. Approx. 10 minutes after the last pressing of a key, an automatic reset to measured value indication is triggered. Any values not confirmed with [OK] will not be saved. VEGACAL 63 • 4 … 20 mA/HART two-wire...
The actual level can then be calculated on the basis of these settings. VEGACAL 63 must be installed. A change of level is necessary for this adjustment. In the main menu item "Basic adjustment", the individual submenu items should be selected one after the other and provided with the correct parameter values.
Page 29
Min. adjustment 0.00 % 0.0 pF 54.5 pF Prepare the adjustment value for editing with [OK]. Move to the selection window with [OK]. Min. adjustment Accept current meas- ured value? Accept? Edit? VEGACAL 63 • 4 … 20 mA/HART two-wire...
Page 30
In general, a period of a few seconds is sufficient to smooth the measured value display. VEGACAL 63 • 4 … 20 mA/HART two-wire...
Page 31
[->] key. Caution: Note the following, if VEGACAL 63 is used as part of an overfill protection system according to WHG: If a linearisation curve is selected, the measuring signal is no longer compulsorily linear proportional to the level.
Page 32
Current output - min. current 3.8 mA Current output - failure < 3.6 mA Special parameters All special parameters are reset to delivery status. Pointer The min. and max. values are reset to the actual value. VEGACAL 63 • 4 … 20 mA/HART two-wire...
0 % = 000.5 hl 100 % = 005.0 hl Diagnostics Basic adjustment Display ▶ Diagnostics Service Info Sensor status Trend recording Pointer Capacit. min.: 65.7 pF Presentation of the trend Capacit. max.: 782.4 pF curve VEGACAL 63 • 4 … 20 mA/HART two-wire...
Page 34
Basic adjustment Display Diagnostics Service ▶ Info Instrument type Date of manufacture Last change using PC Sensor characteristics 04. February 2005 Serial number Software version 04. March 2005 Display now? 12345678 4.10 VEGACAL 63 • 4 … 20 mA/HART two-wire...
They are hence available for multiple use or service purposes. If VEGACAL 63 is equipped with an indicating and adjustment module, the most important data can be read out of the sensor into indicating and adjustment module.
USB cable to the PC VEGACONNECT Sensor VEGACONNECT exter- nally TWIST Fig. 22: Connection via VEGACONNECT externally I²C bus (com.) interface on the sensor I²C connection cable of VEGACONNECT VEGACONNECT USB cable to the PC VEGACAL 63 • 4 … 20 mA/HART two-wire...
With power supply units with integrated HART resistance (internal resistance approx. 250 Ω), an additional external resistance is not necessary. This applies, e. g. to the VEGA instruments VEGATRENN 149A, VEGADIS 371, VEGAMET 381. Common Ex separators are also usually equipped with a sufficient current limitation resistance. In such cases, VEGACONNECT 4 can be connected parallel to the 4 …...
7 Setup with PACTware and other adjustment programs Note: Keep in mind that for setup of VEGACAL 63, DTM-Collection in the actual version must be used. All currently available VEGA DTMs are included as a DTM Collection on a CD. They can be purchased for a token fee from the responsible VEGA agency.
DTM. In many cases, the causes can be determined and faults rectified in this way. However, should these measures not be successful, call the VEGA 24 hour service hotline service hotline in urgent cases under the phone no. +49 1805 858550.
Page 40
Fault messages via the E013 indicating/adjustment no measured value available module à Probe insulation damaged, short-circuit due to permeating, conductive medium à Exchange instrument or return instrument for repair VEGACAL 63 • 4 … 20 mA/HART two-wire...
Reaction after fault rec- described in chapter "Set up" must be carried out again, if necessary. tification 8.3 Exchanging the electronics module If the electronics module is defective, it can be replaced by the user. VEGACAL 63 • 4 … 20 mA/HART two-wire...
If a repair is necessary, please proceed as follows: You can download a return form (23 KB) from our Internet homepage www.vega.com under: "Downloads - Forms and certificates - Repair form". By doing this you help us carry out the repair quickly and without having to call back for needed information.
Correct disposal avoids negative effects to persons and environment and ensures recycling of useful raw materials. Materials: see chapter "Technical data" If you have no possibility to dispose of the old instrument professionally, please contact us concerning return and disposal. VEGACAL 63 • 4 … 20 mA/HART two-wire...
Page 45
1 % of the current measured value Linearity error < 0.25 % of the complete measuring range Ambient conditions Ambient, storage and transport temperature -40 … +80 °C (-40 … +176 °F) Process conditions Process pressure Threaded versions VEGACAL 63 • 4 … 20 mA/HART two-wire...
Page 46
1 x cable entry M16 x 1.5 (cable-ø 3.5 … X mm) External housing 1 x cable entry M16 x 1.5 (cable-ø 3.5 … X mm) Screw terminals for wire cross-section up to 2.5 mm² (AWG 14) VEGACAL 63 • 4 … 20 mA/HART two-wire...
Page 47
M20 x 1.5; 1 x blind stopper M16 x 1.5 Connection cable Wire cross-section 0.5 mm² (AWG 20) Depending on the version M12 x 1, according to DIN 43650, Harting, 7/ 8" FF. VEGACAL 63 • 4 … 20 mA/HART two-wire...
Page 48
IP 40 Materials Housing Inspection window Polyester foil Power supply Operating voltage Non-Ex instrument 12 … 36 V DC EEx-ia instrument 12 … 30 V DC EEx-d-ia instrument 18 … 36 V DC VEGACAL 63 • 4 … 20 mA/HART two-wire...
Page 49
SIL qualification ex factory, the functional safety must be activated by the user via the indicating and adjustment module or via PACTware for applications according to SIL. A suitable cable is the prerequisite for maintaining the protection rating. VEGACAL 63 • 4 … 20 mA/HART two-wire...
Page 50
Depending on the version, instruments with approvals can have different technical data. For these instruments, the corresponding approval documents have to be taken into account. These are part of the delivery or can be downloaded under www.vega.com via "VEGA Tools" and "serial number search" as well as via "Downloads" and "Approvals".
Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellectuelle. Pour plus d'informations, on pourra se référer au site http://www.vega.com VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad industrial. Para mayor información revise la pagina web http://www.vega.com Линии...