Download Print this page

Advertisement

Quick Links

KNX - DALI Broadcast Interface for up to 4 channels
ZDI-DLB4
FEATURES
Control of up to 20 DALI ballasts per channel in up to 4 channels only for logarithmic curve.
Ballast replacement allowed with automatic detection.
Error detection and monitoring (except multiaddress DALI ballasts).
Burn-in, Stand-by and Auto-off functionality for each channel.
Not suitable for emergency lighting control.
Optional manual dimming control.
External 110-230VAC 50/60Hz power supply.
Total data saving on KNX bus failure.
Integrated KNX BCU.
Dimensiones 60 x 90 x 79mm (4,5 unidades DIN).
DIN rail mounting (EN 50022), through pressure.
DALI Standard compatible.
Conformity with the CE directives (CE-mark on the right side).
1. DALI channel output
5. Programming/Test button
Programming/test button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe
mode. If this button is held for more than 3 seconds, the device enters the test mode.
Programming/Test LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. The manual mode
is indicated by the green color. During the start-up (reset or after KNX bus failure) and if the device is not in safe mode, it emits a red flash.
GENERAL SPECIFICATIONS
CONCEPT
Type of device
Voltage (typical)
Voltage range
KNX supply
Maximum
consumption
Connection type
External power supply
Operation temperature
Storage temperature
Operation humidity
Storage humidity
Complementary characteristics
Protection class
Operation type
Device action type
Electrical stress period
Degree of protection
Installation
Minimum clearances
Response on KNX bus failure
Response on KNX bus restart
Operation indicator
Weight
PCB CTI index
Housing material
¹ Maximum consumption in the worst case scenario (KNX Fan-In model)
© Zennio Avance y Tecnología S.L.
2. External supply
6. External supply LED
Voltage
29VDC (typical)
24VDC¹
Edition 5
DALIBOX Broadcast 4CH
1
6
2
3. DALI channel control button
7. Programming/Test LED
DESCRIPTION
Electric operation control device
29VDC SELV
21..31VDC
mA
7
10
Typical TP1 bus connector for 0.80mm Ø rigid cable
110/230VAC 50/60Hz
0°C .. +55°C
-20°C .. +55°C
5 .. 95% (No condens.)
5 .. 95% (No condens.)
Class B
II
Continuous operation
Type 1
Long
IP20, clean environment
Independent device to be mounted inside electrical panels with DIN rail (EN
50022)
Not required
Data saving according to parameterization
Data recovery according to parameterization
The programming LED indicates programming mode (red) and test mode
(green). Each output LED indicates its status (fixed = active output; flashing
= error in the output). Power supply LED indicates the presence of supply
voltage.
124g
175V
PC FR V0 halogen free
Futher information
TECHNICAL DOCUMENTATION
4
3
5
7
Figure 1: DALIBOX Broadcast 4CH
4. DALI channel status LED
8. KNX connector
mW
203
240
www.zennio.com
1
8
Page 1/2

Advertisement

loading

Summary of Contents for Zennio DALIBOX Broadcast 4CH

  • Page 1 Dimensiones 60 x 90 x 79mm (4,5 unidades DIN). • DIN rail mounting (EN 50022), through pressure. • DALI Standard compatible. Figure 1: DALIBOX Broadcast 4CH • Conformity with the CE directives (CE-mark on the right side). 1. DALI channel output 2. External supply 3.
  • Page 2 • The facility must be equipped with a device that ensures the omnipolar sectioning. Installation of a 10A mini-circuit-breaker is recommended. To prevent accidents, it must remain open in case of manipulation of the device. • The device has a short-circuit protection fuse that, in case of activation, should only be rearmed or replaced by the Zennio technical service.
  • Page 3 = error in the output). Power supply LED indicates the presence of supply voltage. Weight 124g PCB CTI index 175V Housing material PC FR V0 halogen free ¹ Maximum consumption in the worst case scenario (KNX Fan-In model) © Zennio Avance y Tecnología S.L. Edition 5 Futher information www.zennio.com Page 1/2...
  • Page 4 • The facility must be equipped with a device that ensures the omnipolar sectioning. Installation of a 10A mini-circuit-breaker is recommended. To prevent accidents, it must remain open in case of manipulation of the device. • The device has a short-circuit protection fuse that, in case of activation, should only be rearmed or replaced by the Zennio technical service.

This manual is also suitable for:

Zdi-dlb4