2. Alarm causes and working status table.
Condition
Circulating pump works properly
Ultrahigh room temperature alarm
Ultrahigh water temperature alarm
Ultralow water temperature alarm
Ambient temperature sensor failure
Water temperature sensor failure
Switch type flow alarm/ liquid level alarm
Sensor type flow alarm
Chiller power failure
Note: The alarm output port is connected with a set of normally open and normally closed
contacts of the relay inside the machine. The working current should be smaller than 3A while
the working voltage should be smaller than 300V.
VII.Maintenance
The equipment must be shut down for maintenance, and the power supply must be cut
off. The operation can only be carried out after 3 minutes, otherwise there will be a risk of
electric shock. When the room temperature is lower than 2°C, the internal water must be
drained when the machine is shut down for a long time.
Regularly disassemble the filter gauze for cleaning and use a compressed air gun to blow
away the dust on the condenser (about 1 week is suggested and the air filter must not be
missing for a long time).
Display
Alarm
Buzzer
code
E1
Sounds
E2
Sounds
E3
Sounds
E4
Sounds
E5
Sounds
E6
Sounds
E7
Sounds
14
TY-JS-20319-003
OUT H1、H2
OUT H1、H3
Disconnection
Breakover
Breakover
Disconnection
Breakover
Disconnection
Breakover
Disconnection
Breakover
Disconnection
Breakover
Disconnection
Breakover
Disconnection
Breakover
Disconnection
Breakover