Upon receiving the alarm, the wall unit will remove
the "Y" call from the CCM, resetting the status of the
CCM. The alarm will stay present on the wall unit until
manually cleared. This operation has no configurable
parameters.
Economizer Damper
When the controller commands the economizer damper
actuator to a position other than 0% and the damper
switch indicates the damper is not open, after a delay
of 20 seconds (Open Del on display) the controller
will generate a damper failed to open alarm. When the
controller commands the economizer damper actuator
to the 0% position and the damper switch indicates
the damper is not closed, after a delay of 300 seconds
(Close Del on display) the controller will generate a
damper failed to close alarm.
To adjust these values:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to Sys Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Alarm Config
(A8); press ENTER key.
5. Press ENTER key to scroll to desired value Open
Del or Close Del (see Figure 2.7).
6. Press UP or DOWN keys to adjust value.
7. Press ENTER key to save.
FIGURE 2.7
Adjusting Damper Alarm Values
Manual 2100-665A
Page
28 of 51
Freezestat
When the coil temperature is below 30°F, the unit
will generate a Freeze alarm on the TEC-EYE
Freeze Temp alarm on the LC6000. This will operate
the blower and turn off the compressor.
When the coil temp is above 55°F, the alarm must be
reset with the TEC-EYE
TM
the alarm at the LC6000 as well. The blower and
compressor will then be available to operate as needed
for cooling.
To adjust freezestat values:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to Sys Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Alarm Config
(A8); press ENTER key.
5. Press ENTER key to scroll to desired value Low
Temp, Reset Temp or Reset Del (see Figure 2.7).
6. Press UP or DOWN keys to adjust value.
7. Press ENTER key to save.