W**Lap Series - Bard MULTI-TEC W18AAPA Installation And Service Instructions Manual

Hide thumbs Also See for MULTI-TEC W18AAPA:
Table of Contents

Advertisement

Electrical Specifications – W**LAP Series
No.
Rated
Field
MODEL
Volts &
Power
Phase
Circuits
W18LAPA00,A0Z
1
A05
1
230/208-1
A08
1
A10
1
W24LAPA00, A0Z
1
A05
1
230/208-1
A08
1
A10
1
W24LAPB00, B0Z
1
230/208-3
B06
1
W24LAPC00, C0Z
1
460-3
C06
1
W30LAPA00, A0Z
1
A05
1
A08
230/208-1
1
A10
1
A15
1 or 2
W30LAPB00, B0Z
1
B09
230/208-3
1
B15
1
W30LAPC00, C0Z
1
C09
460-3
1
C15
1
W36LAPA00, A0Z
1
A05
1
230/208-1
A10
1
A15
1 or 2
W36LAPB00, B0Z
1
B09
230/208-3
1
B15
1
W36LAPC00, C0Z
1
C09
460-3
1
C15
1
W42LAPA00, A0Z
1
A05
1
230/208-1
A10
1
A15
1 or 2
W42LAPB00, B0Z
1
B06
1
230/208-3
B09
1
B15
1
W42LAPC00, C0Z
1
C09
460-3
1
C15
1
W48LAPA00, A0Z
1
A05
1
230/208-1
A10
1
A15
1 or 2
W48LAPB00, B0Z
1
B06
1
230/208-3
B09
1
B15
1
W48LAPC00, C0Z
1
C09
460-3
1
C15
1
W60LAPA00, A0Z
1
A05
1
230/208-1
A10
1
A15
1 or 2
W60LAPB00, B0Z
1
B06
1
230/208-3
B09
1
B15
1
W60LAPC00, C0Z
1
C09
460-3
1
C15
1
W72LAPA00, A0Z
1
A05
1
230/208-1
A10
1 or 2
A15
1 or 2
W72LAPB00, B0Z
1
B06
1
230/208-3
B09
1
B15
1
W72LAPC00, C0Z
1
C09
460-3
1
C15
1
 Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
 Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
 These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor
sizing.
CAUTION: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to Note 8 of Table 310 regarding Ampacity
Adjustment Factors when more than three current carrying conductors are in a raceway.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National
Electrical Code and all local codes.
TABLE 1.2
Single Circuit
Maximum
Minimum
Field
External
Circuit
Power
Fuse or Ckt.
Ampacity
Wire Size
Brkr.
16
20
12
30
30
10
46
50
8
56
60
6
21
30
10
30
30
10
46
50
8
56
60
6
15
20
12
22
25
10
9
15
14
11
15
14
26
35
8
32
35
8
47
50
8
58
60
6
84
90
4
19
20
12
33
35
8
51
60
6
9
15
14
17
20
12
26
30
10
29
35
8
32
35
8
58
60
6
84
90
4
23
30
10
33
35
8
51
60
6
11
15
14
17
20
12
26
30
10
32
50
8
32
50
8
58
60
6
84
90
4
25
35
8
25
35
8
33
35
8
51
60
6
12
15
14
17
20
12
26
30
10
34
50
8
34
50
8
58
60
6
84
90
4
26
35
8
26
35
8
33
35
8
51
60
6
12
15
14
17
20
12
26
30
10
38
60
8
38
60
8
60
60
6
86
90
3
27
40
8
27
40
8
35
40
8
53
60
6
14
20
12
18
20
12
27
30
10
58
60
6
58
60
6
62
70
6
88
90
3
40
60
8
40
60
8
40
60
8
55
60
6
18
25
10
18
25
10
27
30
10
 Minimum
 Maximum
Circuit
External Fuse or
Ampacity
Ckt. Breaker
Ground
Wire
Ckt. A
Ckt. B
Ckt. A
12
10
10
10
10
10
10
10
12
10
14
14
10
10
10
10
8
58
26
60
12
10
10
14
12
10
10
10
10
8
58
26
60
10
10
10
14
12
10
10
10
10
8
58
26
60
10
10
10
10
14
12
10
10
10
10
8
58
26
60
10
10
10
10
14
12
10
10
10
10
8
60
26
60
10
10
10
10
12
12
10
10
10
8
58
26
60
8
58
52
60
10
10
10
10
10
10
10
Dual Circuit
Field Power
Ground
Wire Size
Wire Size
Ckt. B
Ckt. A
Ckt. B
Ckt. A
30
6
10
10
30
6
10
10
30
6
10
10
30
6
10
10
30
6
10
10
30
6
10
10
60
6
6
10
Manual 2100-665A
Page
19 of 51
Ckt. B
10
10
10
10
10
10
10