4. Press UP or DOWN keys to scroll to Alarm Config
(A7); press ENTER key.
5. Press ENTER key to scroll to desired value OAT,
Diff, Del, LDel or Two Count Del (see Figure 11).
6. Press UP or DOWN keys to adjust value.
7. Press ENTER key to save.

Refrigerant High Pressure

When the wall-mount unit receives a signal from the
compressor control module (CCM) indicating a high
pressure event, the wall-mount unit will generate an
alarm. Upon receiving the alarm, the wall-mount unit
will remove the "Y" call from the CCM, resetting the
status of the CCM. The alarm will stay present on the
wall-mount unit until manually cleared. This operation
has no configurable parameters.

Economizer Damper

When the controller commands the economizer damper
actuator to a position other than 0% and the damper
switch indicates the damper is not open, after a delay
of 20 seconds (Open Del on display) the controller
will generate a damper failed to open alarm. When the
controller commands the economizer damper actuator
to the 0% position and the damper switch indicates
the damper is not closed, after a delay of 300 seconds
(Close Del on display) the controller will generate a
damper failed to close alarm.
To adjust these values:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to Sys Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Alarm Config
(A8); press ENTER key.
5. Press ENTER key to scroll to desired value Open
Del or Close Del (see Figure 12).
6. Press UP or DOWN keys to adjust value.
7. Press ENTER key to save.
FIGURE 12
Adjusting Damper Alarm Values
Manual 2100-665D
Page
12 of 26

Freezestat

When the coil temperature is below 30°F, the unit will
generate a Freeze alarm on the TEC-EYE and a Freeze
Temp alarm on the LC6000. This will operate the
blower and turn off the compressor.
The alarm will be automatically reset when the coil
temperature rises above 55°F or after a 5-minute delay
while the temperature is above 30°F.
To adjust freezestat values:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to Sys Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Alarm Config
(A8); press ENTER key.
5. Press ENTER key to scroll to desired value Low
Temp, Reset Temp or Reset Del (see Figure 12).
6. Press UP or DOWN keys to adjust value.
7. Press ENTER key to save.