Page 3
Essential Instructions Read this page before proceeding! Emerson designs, manufactures and tests its products to meet many national and international stan- dards. Because these sensors are sophisticated technical products, you MUST properly install, use, and maintain them to ensure they continue to operate within their normal specifications. The following instructions MUST be adhered to and integrated into your safety program when installing, using, and maintaining Rosemount products.
Quick Start Guide Installation 00825-0100-3402 May 2019 Section 2: Installation Unpacking and Inspection Inspect the outside of the carton for any damage. If damage is detected, contact the carrier immediately. Inspect the instrument and hardware. Make sure all items in the packing list are present and in good condition.
Installation Quick Start Guide May 2019 00825-0100-3402 Installation and Retraction of Sensor Figure 2-3 Label 2.1.1 Installation Retraction assembly kit (PN 23765-00) consists of items 1 through 7 shown in Figure 2-4 as well as a hex key and pipe tape. The sensor assembly includes items 8 through 11. IMPORTANT Do not remove or alter the guard (10) on the sensor tube (9).
Page 11
Quick Start Guide Installation 00825-0100-3402 May 2019 Slide the handle lock up on the ball valve handle and close the ball valve (2). If the process will be restarted before the sensor is installed, make sure the system pressure is at or below 542 kPa abs (64 psig) before proceeding.
Page 12
Failure to withdraw the sensor completely may result in damage to the electrodes when the valve is closed. Unscrew the packing adapter (3) from the ball valve (2) to remove the sensor and retraction assembly. Figure 2-6 Rosemount 402 Contacting Conductivity Sensor in Retracted Position Installation...
Quick Start Guide Wiring 00825-0100-3402 May 2019 Section 3: Wiring Wiring for Rosemount 402/402VP For other wiring diagrams not shown below, please refer to the Liquid Transmitter Wiring Diagrams. Figure 3-1: Wire color and connections in sensor Figure 3-2: Wiring for integral junction box...
Page 14
Wiring Quick Start Guide May 2019 00825-0100-3402 Figure 3-3: Wiring for Rosemount 56 and 1056 transmitters Figure 3-4: Wiring for Rosemount 56 and 1056 transmitters Wiring...
Page 15
Quick Start Guide Wiring 00825-0100-3402 May 2019 Figure 3-5: Wiring for Rosemount 5081 transmitter 3.1.1 Wiring through a Junction Box If wiring connections are made through a remote junction box (PN 23550-00), wire point-to-point. Use interconnecting cable 23747-00 (factory-terminated) or 9200275 (no terminations). Figure 3-6: Pin out diagram for Rosemount 402VP contacting conductivity sensors with Variopol cable connection Wiring...
Page 16
Wiring Quick Start Guide May 2019 00825-0100-3402 Wiring...
Calibrating the sensor Rosemount 402 conductivity sensors are calibrated at the factory and do not need calibration when first placed in service. Simply enter the cell constant printed on the label into the transmitter. After a period of service, the sensor may require calibration. The sensor can be calibrated against a solution having known conductivity or against a referee meter and sensor.
Page 18
Calibration and Maintenance Quick Start Guide May 2019 00825-0100-3402 Calibration and Maintenance...
Quick Start Guide Troubleshooting 00825-0100-3402 May 2019 Section 5: Troubleshooting Troubleshooting Table 5-1: Troubleshooting Trouble Probable Cause Remedy Wiring is incorrect. Verify wiring. Temperature element is open or shorted. Check temperature element for open or short circuits. See Figure 5-1. Off-scale reading Sensor is not in process stream.
Page 20
Troubleshooting Quick Start Guide May 2019 00825-0100-3402 5.1.1 Checking the temperature element Disconnect leads and measure resistance shown. The measured resistance should be close to the value in the table. Figure 5-1 Checking the temperature element Temperature Resistance in ohms (°C) Pt 100 Pt 1000...
Need help?
Do you have a question about the Rosemount 402 and is the answer not in the manual?
Questions and answers