Download Print this page

Technical Data - S+S Regeltechnik PREMASGARD 211 Series Operating Instructions, Mounting & Installation

Pressure and differential pressure measuring transducers, including connection set, compact form, adjustable, calibratable, with multi-range switching and active output
Hide thumbs Also See for PREMASGARD 211 Series:

Advertisement

G
®
PREMASGARD
The calibrateable compact pressure sensors of the PREMASGARD
ranges, 2 switchable output signals (16 devices in one) and with or without optional display and are used for measuring above-atmospheric, below-
atmospheric, or differential pressures and Volume flow in air. The piezo-resistive measuring element is temperature- compensated and guarantees a
high degree of reliability and accuracy. These pressure transmitters have a pushbutton for manual zero point calibration and an adjustable offset.
Applications of these pressure sensors are in clean room, medical and filter technology, in ventilation and air conditioning ducts, in spray booths, in
large-scale catering facilities, for monitoring filters, for level measurement or for triggering frequency converters. Media measured with these
pressure transducers are air (non-precipitating), or other gaseous non-aggressive, non-combustible media. The differential pressure sensor is
supplied including connection set ASD-06 (2 m connection hose, two pressure connection nipples, screws). You can find further device types under
®
111x ⁄ 112x ⁄ 112x - SD (l variant with 2-wire connection).
PREMASGARD

TECHNICAL DATA

Power supply:
Working resistance:
Load resistance:
Power consumption:
Current consumption:
Measuring function:
Measuring ranges:
Output:
Electrical connection:
Media temperature:
Pressure connection:
Type of pressure:
Medium:
Accuracy:
Zero point offset:
Above- ⁄ below-atmospheric pressure: ± 50 kPa
Long-term stability:
Signal filtering:
Hysteresis:
Media contacting parts:
Temperature drift values:
Linearity:
Housing:
Housing dimensions:
Cable connection:
Electrical connection:
Humidity:
Protection class:
Protection type:
Standards:
Features:
ACCESSORIES
211x ⁄ 212x ⁄ 212x - SD
24 V AC/DC (± 10 %)
R
(Ohm) = 25 ...450 Ohm for I variant
a
R
> 25 kOhm for U variant
L
< 1 W at 24 V DC; < 2 VA at 24 V AC
< 45 mA
Differential pressure, volume flow (square root output signal)
multi-range switching with 8 switchable measuring ranges (see table)
switchable 0 -10 V ⁄ 4...20 mA (via DIP switches)
3-wire connection
–20...+50 °C (temperature-compensated 0...+50 °C)
with connection nozzles for pressure hose Ø 6 mm
differential pressure
clean air and other non-aggressive, non-combustible gases
Type 2110 ⁄ 2120 ⁄ 2120 - SD (100 Pa): typically ± 3 Pa at +25 °C
Type 2111 ⁄ 2121 ⁄ 2121 - SD (1000 Pa): typically ± 10 Pa at +25 °C
Type 2115 ⁄ 2125 ⁄ 2125 - SD (5000 Pa): typically ± 35 Pa at +25 °C
compared to the calibrated reference device
± 10 % of final value
± 1 % per year
switchable 1 s ⁄ 10 s (via DIP switches)
0.3 % of final value
Brass, Ni, Duroplast, Si, epoxy, RTV, BSG, UV silicone gel
± 0.1 % of final value ⁄ °C
< ± 1 % of final value
plastic, UV-resistant, material polyamide, 30 % glass-globe reinforced,
colour traffic white (similar to RAL 9016),housing cover for display is transparent!
Type 211x ⁄ 212x:
Type 212x - SD:
72 x 64 x 37.8 mm (Tyr 1 / Tyr 01 without display)
72 x 64 x 43.3 mm (Tyr 1 / Tyr 01 with display)
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
0.14 - 1.5 mm², via terminal screws
< 95 % r. H., non-precipitating air
III (according to EN 60 730)
Type 211x ⁄ 212x:
Type 212x - SD:
CE conformity, electromagnetic compatibility according to EN 61 326, EMC directive 2014 ⁄ 30 ⁄ EU
two-line display with illumination, cutout approx. 36 x 15 mm (W x H),
to display ACTUAL pressure
see table
®
211x ⁄ 212x ⁄ 212x - SD series are equipped with 8 switchable measuring
with quick-locking screws
(slotted/Phillips head combination)
with snap-on lid
IP 67 (according to EN 60 529)* Housing tested,
TÜV SÜD, Report No. 713139052 (Tyr 1)
IP 54 (according to EN 60 529)* Housing tested,
TÜV SÜD, Report No. 713160960A (Tyr 01)
* Housing in the built-in state
10
Rev. 2021 - V21

Advertisement

loading

This manual is also suitable for:

Premasgard 212 seriesPremasgard 212 sd series