Download Print this page

Technical Data - S+S Regeltechnik PREMASGARD 1140 Operating Instructions, Mounting & Installation

Advertisement

Available languages

Available languages

  • ENGLISH, page 10
G
®
PREMASGARD
1140 ⁄ PREMASREG
Quality product for HVAC sector, accuracy ± 1.5 % or ± 3 %
The calibrateable compact pressure sensors PREMASGARD
display (4 devices in one).
Electronic pressure sensors and switches PREMASREG® 1141 are equipped with four switchable measuring ranges, one switching out-
put and one continuous output, and a display for setting the switchpoint and to display the ACTUAL pressure (four devices in one plus
differential pressure switch ⁄ differential pressure monitor and continuous pressure sensor in one and the same device).
The pressure sensor is used for above-atmospheric, below-atmospheric, or differential pressure measurement in clean air with limit value
switching. The piezo-resistive measuring element guarantees a high degree of reliability and accuracy. Applications of these pressure
sensors are in clean room, medical and filter technology, in ventilation and air conditioning ducts, in spray booths, in large-scale catering
facilities, for monitoring filters, for level measurement or for triggering frequency converters. Media measured with these pressure
transducers are air (non-precipitating), or other gaseous non-aggressive, non-combustible media. The pressure sensor has a manual zero
point pushbutton and an offset potentiometer for final value and switchpoint correction. Fine adjustment by the user is possible at any
time. A connection set ASD-06 (2 m connection hose, two pressure connection nipples, screws) is included in the scope of supply.
TECHNICAL DATA:
Power supply: ..................................24 V AC (± 20 %) and 15 ... 36 V DC (± 10 %)
Power consumption: ....................< 1 VA ⁄ 24 V DC, < 2.2 VA ⁄ 24 V AC
Measuring ranges: ........................multi-range switching with 4 switchable measuring ranges
Media temperature: ......................0 ... + 50 °C
Pressure connection: ...................4 ⁄ 6 x 11 mm (hoses Ø = 4 ⁄ 6 mm), metal pressure connection nozzles
Type of pressure: ...........................differential pressure
Above- ⁄ below-
atmospheric pressure: ................max. ± 200 hPa
Signal filtering: ................................switchable 1 s ⁄ 10 s
Medium: ..............................................clean air and other non-aggressive,
®
PREMASGARD
1140
Output signal: ...................................0 -10 V or 4 ... 20 mA
Electrical connection:...................2- or 3-wire connection
Accuracy: ...........................................± 1.5 % of final value (at 20°C) with display
Sum of
Linearity+hysteresis: ...................< ± 1 % of final value with display
Temperature drift values: ..........± 0.1 % ⁄ °C with display
Zero point offset: ...........................< ± 0.7 % of final value with display
®
PREMASREG
1141
Output signal: ...................................0 -10 V
Electrical connection:...................3-wire connection (U)
Accuracy: ...........................................± 1.5 % of final value (at 20°C)
Sum of
Linearity + hysteresis: .................< ± 1 % of final value
Temperature drift values: ..........± 0.1 % per °C
Zero point offset: ...........................< ± 0.7 % of final value
Enclosure: .................................... impact-resistant plastic, material polyamide, 30 % glass-globe-reinforced,
Dimensions: ................................. 108 x 72.5 x 70 mm (Thor II)
Electrical connection: ................ 0.14 - 1.5 mm², via removable plug-in screw terminals
Cable gland: ................................. M 16, including strain relief
Humidity: ...................................... < 95 % r.H., non-precipitating air
Protection class: ........................ III (according to EN 60 730)
Protection type:.......................... IP 65 (according to EN 60 529)
Standards: ................................... CE conformity, according to EMC directive 2004 ⁄ 108 ⁄ EC,
Features: ..................................... two-line display with illumination, 37 x16 mm (W x H),
ACCESSORIES: ........................... including connection set ASD - 06 (nipple straight) – (included in the scope of delivery)
®
1141
see table
non-combustible gases
± 3.0 % of final value (at 20°C) without display
(optional ± 1.5 % of final value)
< ± 2 % of final value without display, standard
(optional ± 1 % of final value)
± 0.3 % ⁄ °C without display
< ± 1.5 % of final value without display
1 changeover contact (24 V ⁄ 1 A)
with quick-locking screws, colour pure white (similar RAL 9010)
according to EN 61326-1: 2006, according to EN 61326-2-3: 2006
for displaying ACTUAL pressure and ⁄ or SETPOINT pressure respectively undercutting
or exceeding the measuring range
connection nipple ASD - 07 (at 90 degree angle)
pressure outlet DAL -1 for ceiling or in-wall installation (e.g. in clean rooms)
®
1140 (series) are equipped with four switchable measuring ranges and with
10

Advertisement

loading

This manual is also suitable for:

Premasreg 1141