G
THERMASGARD
®
Calibrateable tube contact temperature measuring transducers THERMASGARD
or remote sensor, continuous output, strap and terminal box enclosure made of impactresistant plastic, enclosure cover with quicklocking
screws, optional with or without display. This surface contact feeler is used for temperature detection on piping and tubes (e.g. coldwater
and hotwater), or on heating sections for heating system control. The tube sensors are factorycalibrated. Adjustment ⁄ fine adjustment by
the user is possible (range and zero point are adjustable).
TECHNICAL DATA:
Power supply: .............................. 24 V AC ⁄ DC ± 10 % for output 0 10 V
Sensor: ......................................... Pt1000, DIN EN 60751, class B
Measuring ranges: ..................... multi-range switching with 8 switchable measuring ranges,
Output: ......................................... 0 10 V or 4... 20 mA
Ambient temperature: .............. measuring transducer 30 ...+ 70 °C
Connection type: ........................ 2 or 3 wire connection
Process connection: .................. endless metal strap and metal tightener
Strap dimensions: ...................... Ø = 13 92 mm (1 ⁄ 4 3"),
Connecting head: ...................... plastic, material polyamide, 30 % glassglobereinforced,
Dimensions: ................................. 72 x 64 x 39.4 mm
Cable gland: ................................. M 16, including strain relief
Connecting cable: ....................... silicone, 1.5 m, SiHF, 2 x 0.25 mm²,
(ALTM 2 only)
Electrical connection: ................ 0.14 1.5 mm² via terminal screws
Insulating resistance: ................ ≥ 100 MΩ, at 20 °C (500 V DC)
Humidity: ...................................... < 95 % r. H., nonprecipitating air
Protection class: ........................ III (according to EN 60 730)
Protection type:.......................... IP 65 (according to EN 60 529)
Standards: ................................... CE conformity,
Optional: ....................................... singleline display with illumination,
Type ⁄ WG1
ALTM 1-I
ALTM 1-U
ALTM 2-I
ALTM 2-U
ALTM xx - Display
Optional:
Extra charge:
Accessories:
ALTM
15 36 V DC for output 4 ... 20 mA
(depending on working resistance)
see table (other ranges optional)
ALTM 1 (compact variant):
T
up to 100°C, operating range 50 ...+ 100 °C
max
ALTM 2 (remote variant):
T
over 100°C, operating range 50 ...+ 150 °C
max
with manual zero point correction (± 10 K)
(included in the scope of delivery)
length L = 300 mm
with quick-locking screws,
colour pure white (similar RAL 9010)
ends stripped, with wire end sleeves
(optional Teflon up to 250 °C or glass fibre with steel wire mesh up to 350 °C)
electromagnetic compatibility
according to EN 61326: 2006,
according to EMC directive 2004 ⁄ 108 ⁄ EC
cutout 37 x15 mm (W x H),
for displaying actual temperature
Sensor
Pt 1000
Pt 1000
Pt1000
Pt1000
Singleline display with illumination
Other measuring ranges on request.
2wire connecting leads (silicone) per running meter
Rolled ⁄ stamped humidity tight
Heatconductive paste, set
®
ALTM with eight switchable measuring ranges, internal
Output
4...20 mA
0 10 V
4...20 mA
0 10 V
Model
Compact
Compact
Remote sensor
Remote sensor