PC5010 Device Ratings (@ 12 V
• LCD5500 Keypad: 50 mA
• PC5532 Keypad: 45 mA
• PC5516 Keypad: 45 mA
• PC5508 Keypad: 45 mA
• LCD5500Z Keypad: 85 mA
• PC5532Z Keypad: 85 mA
• PC5516Z Keypad: 85 mA
• PC5508Z Keypad: 85 mA
• PC5108 Zone Module: 35 mA
• PC5204 Output Module: 20 mA
• PC5720 Fire/Printer/DVACS Module: 85mA standby, 100mA with printer
Other Devices
Read the manufacturer's literature carefully to determine the maximum current requirement (during
activation or alarm) and use this value for loading calculations. Do not allow connected devices to exceed
the system capabilities during any possible operational mode.
2.5

Assigning Zones to Zone Expanders

The main panel contains zones 1 to 8. Additional zone expanders may be added to increase the number
of zones on the system. Each zone expander consists of two groups of 4 zones and each group must be
configured to assign the specific zones to the expander. This is done by setting the jumpers located on
the expander to the proper settings.
Before a zone expander will work properly the jumpers must be set so the panel can determine the
correct zone assignment .
You cannot change the zone assignment of the PC5720 module. PC5720 zones are always assigned to
system zones 09-16. Refer to the PC5720 Installation Manual for more information.
The following are the jumper settings for different zone assignments:
J1, J2 and J3 set system zone assignments for expander zones 1-4
J4, J5 and J6 set system zone assignments for expander zones 5-8
The following are diagrams of the PC5108 and PC5700 zone expander modules and where the jumper
switches are located. Refer to the Installation Instructions of each module for more information.
There are two sets of jumpers, one set for the first 4 zones of the expander and one set for the other 4 zones .
In these two diagrams the jumpers settings shown indicate the first group of four zones of the expander
will be zones 9 to 12 and the second group of 4 zones will be 13 to 16. A group of zones can be disabled
if they are not required for the installation.
In the above diagram the jumpers settings shown indicate the first group of four zones of the expander
will be zones 9 to 12 and the second group of 4 zones will be 13 to 16.
A group of zones can be disabled if they are not required for the installation.
T
I
N
G
)
DC
Jumpers
J1/J4
J2/J5
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
S
T
• PC5208 Output Module: 50 mA
• PC5132 Wireless Module: 125 mA
• PC5100 Addressable Device Interface Module: 40 mA
• Escort5580 Module: 150 mA
• PC5928 Audio Interface Module: 65 mA
• PC5921 Intercom Audio Station: 20 mA
• PC5921 EXT Door Box Audio Station: 20 mA
• PC5921 EXT/R Door Box Audio Station: 35 mA
• PC5400 Printer Module: 65 mA
• PC5700 Fire Module: 150mA
System Zones Assigned
J3/J6
ON
Zones disabled
ON
Zones disabled
ON
Zones 09 - 12
ON
Zones 13 - 16
OFF
Zones 17 - 20
OFF
Zones 21 - 24
OFF
Zones 25 - 28
OFF
Zones 29 - 32
8