[10] Latched System Event (Strobe Output) The output will activate when any of the selected system
events (alarms) occur on the system. In the armed state, the output will deactivate only once the system is
disarmed.
If an alarm activates this output in the disarmed state, the output will deactivate if a user enters a valid
access code while the Bell Cut-off timer is counting down. The output will also deactivate if someone
arms the system after the Bell Cut-off has expired. This output can be used to indicate that an alarm has
occurred before entering the premises.
The PGM attributes for this option, programmed in Sections [141] to [154], differ from the standard selection of
attributes. Program which events will activate the output by selecting some or all of the following attributes:
[1] ...... Burglary (Delay, Instant, Interior, Stay/Away and 24 Hour Burglary Zones)
[2] ...... Fire (Fire Keys, Fire Zones)
[3] ...... Panic (Panic Keys and Panic Zones)
[4] ...... Medical (Auxiliary Keys, Medical and Emergency Zones)
[5] ...... Supervisory (Supervisory, Freezer and Water Zones)
[6] ...... Priority (Gas, Heat, Sprinkler and 24 Hour Latching Zones)
[7] ...... Holdup (Holdup zones)
This output will activate for silent and audible alarms or medical conditions only. It will not activate
during pre-alert or delays.
[11] System Tamper The PGM Output will activate when any Tamper condition is present and will
deactivate when all Tamper conditions are cleared.
[12] TLM and Alarm The PGM Output will activate when a telephone line fault condition is present AND
an alarm occurs. The PGM Output will remain active until an access code is entered. The output will
activate for both audible and silent alarms if a TLM trouble is present.
This output will activate for all audible and silent alarms except Duress.
[13] Kissoff The PGM Output will activate for two seconds after the panel receives the kissoff from the
central station.
[14] Ground Start The PGM Output will activate for two seconds before the panel attempts to dial to
obtain dial tone on Ground Start telephone equipment. Two second pauses should be inserted at the
beginning of the phone number when using this option.
[15] Remote Operation (DLS-1 Support) This output can be activated and deactivated remotely using
DLS software.
[16] LINKS1000 Support (PGM1 Only) The PGM output will be used as a data wire to communicate
phone number information for the LINKS1000 cellular unit.
[17] Away Armed The PGM will activate when the system is armed with the Stay/Away zones activated.
[18] Stay Armed The PGM will activate when the system is armed with the Stay/Away zones bypassed.
[19] [ ] [7] [1] Command Output Option #1
[20] [ ] [7] [2] Command Output Option #2 Press [ ] [7] [2] [Access Code, if required] to activate any
output programmed as one of PGM output option [03] or [20].
Traditionally, [ ] [7] [2] has been reserved for resetting smoke detectors. Smoke detectors should now be
programmed as output [03] "Sensor Reset".
Only ONE of options [03] Sensor Reset, [04] 2-Wire Smoke and [20] [ ] [7] [2] Command Output Option
#2 may be programmed on the same system.
[21] [ ] [7] [3] Command Output Option #3
[22] [ ] [7] [4] Command Output Option #4 These outputs are user-initiated by entering [ ] [7] [1-4] at
any keypad. When any output is activated, three acknowledgment beeps are heard.
[23] Silent 24 Hour (PGM2 Only) A Panic button may be placed on the PGM2 terminal for use as a silent
24 hour Panic. The keypad will not indicate the alarm in any way and the Bell will remain silent but the PGM2
Alarm reporting code will be sent to the central station. PGM output option [23] will not activate other
programmable outputs of any kind. This input does not follow Swinger Shutdown.
[24] Audible 24 Hour (PGM2 Only) A Panic button may be placed on the PGM2 Terminal for use as an
Audible 24 Hour Panic. When the button is pressed, LCD keypads will indicate "System in Alarm", the bell will
sound until the Bell Cut-off expires, and the PGM2 Alarm reporting code will be sent to the central station. PGM
output option [24] will not activate other programmable outputs except for outputs programmed as [01]. This
input does not follow Swinger Shutdown.
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Main Board PGM Outputs ...................................... Section [009]
PC5208 PGM Output Options ................................ Section [010]
PC5204 PGM Output Options ................................ Section [011]
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
A
M
D
E
32
S
C
R
I
P
T
I
O
N
S

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents