S3 Logic Inputs Setpoints - GE Multilin 750 Quick Reference Manual

Feeder management relay
Hide thumbs Also See for Multilin 750:
Table of Contents

Advertisement

Application example
(for a 138 kV system, 13.8 kV / 120 = 115 V)
VT
RATIO: "120:1" (14.4 kV VT
For the case where Bus VTs are connected in Wye, the system settings are:
VT CONNECTION
NOMINAL VT SECONDARY
entered. For a 13.8 kV system, we have 13.8kV ø-ø
120 = 66.4 V)
VT
RATIO: "120:1" (14.4 kV VT
The 750/760 was designed to display primary system values. Current and voltage
measurements are performed at secondary levels, which the relay transforms to primary
values using CT and VT ratios, as well as nominal secondary values.
Configuring the relay for current measurement is simple and it only requires setting the CT
ratios. CT inputs can be 1 A or 5 A and must be specified when the relay is purchased. There
is additional flexibility with regards to the VT inputs, as nominal values are not required
before the relay is ordered; therefore, more settings are needed to prepare the relay for
voltage measurements.
Make the following change in the
reflect the power system:
NOMINAL
FREQ: "60 Hz"
Using EnerVista 750/760 Setup software, the settings described above can be set as
follows:
1.
Select the Setpoints > S2 System Setup menu item. The following window will appear:
2.
Change the values of phase CT primary, VT connection type, nominal VT secondary
voltage, VT ratio, and system frequency as required, then press the Save button.

S3 Logic Inputs setpoints

The S3 setpoints page is for entering the characteristics of the logic inputs. In our example,
these characteristics are specified under the Control System Requirements heading.
Program the S3 setpoints as indicated.
To properly configure the relay to respond to digital inputs, they need to be defined as
follows:
42
/ 120 V VT
primary
TYPE: "Wye"
VOLTAGE: "66.4 V" (the phase-to-neutral voltage must be
/ 120V VT
primary
S2 SYSTEM SETUP
)
secondary
7.97kV ø-N; therefore, 7.97kV /
)
secondary
POWER SYSTEM
750/760 Quick Reference Guide
setpoints page to

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multilin 760

Table of Contents