Application example
LOCAL
MODE: "Input 3"
RESET: "Input 6"
REMOTE
OPEN: "Input 4"
REMOTE
CLOSE: "Input 5"
If, for example, the same logic input would be needed to perform the functionality of Close
and Reset, then the following should have been entered:
RESET: "Input 5"
REMOTE
CLOSE: "Input 5"
Using the EnerVista 750/760 Setup software, the same setpoints can be changed as
follows:
1.
Select the Setpoints > S3 Logic Inputs > Logic Input Setup menu item. The following
window will appear:
2.
Change the corresponding setpoints as indicated, and then press Save. These
setpoints are only to identify the Logic Inputs, and to define their asserted logic.
To complete the setpoints corresponding to Logic Inputs, define their functionality as
follows:
1.
Input 2 will be used to monitor the status of the breaker. Select the Setpoints > S3
Logic Inputs > Breaker Functions menu item to display the following window:
2.
Change the corresponding setpoints, and then press Save.
44
750/760 Quick Reference Guide